114 Electrical installationDrive-to-drive link (XD2D)The drive-to-drive link is a daisy-chained RS-485 transmission line that allows basicmaster/follower communication with one master drive and multiple followers.Set termination activation jumper J3 (see section Jumpers and switches above) nextto this terminal block to the ON position on the drives at the ends of the drive-to-drivelink. On intermediate drives, set the jumper to the OFF position.Use shielded twisted-pair cable (~100 ohm, for example, PROFIBUS-compatiblecable) for the wiring. For best immunity, high quality cable is recommended. Keep thecable as short as possible; the maximum length of the link is 50 meters (164 ft). Avoidunnecessary loops and running the cable near power cables (such as motor cables).The following diagram shows the wiring of the drive-to-drive link.DIIL input (XD24:1)The DIIL input can be selected as the source of, for example, an emergency stopcommand or an external event. See the firmware manual for more information.J3 J3XD2DXD2DJ3XD2DABGNDB 123ABGNDB 123ABGNDB 123. . .. . .. . .. . .