Technical data 197Electrical power network specificationVoltage (U1 ) ACS880-01-xxxx-2 drives: 208 … 240 V AC 3-phase+10%…-15%. This is indicated in the type designationlabel as typical input voltage level 3 230 V AC.ACS880-01-xxxx-3 drives: 380 … 415 V AC 3-phase+10%…-15%. This is indicated in the type designationlabel as typical input voltage level 3 400 V AC.ACS880-01-xxxx-5 drives: 380 … 500 V AC 3-phase+10%…-15%. This is indicated in the type designationlabel as typical input voltage levels 3 400/480/500V AC.ACS880-01-xxxx-7 drives: 525 … 690 V AC 3-phase+10%…-15%. This is indicated in the type designationlabel as typical input voltage levels 3 525/600/690V AC.Network type TN (grounded) and IT (ungrounded) systems.However, 690 V drives must not be installed on corner-grounded TN systems or corner-grounded IT systems.Rated conditional short-circuitcurrent (IEC 61439-1)65 kA when protected by fuses given in the fuse tablesShort-circuit current protection(UL 508C,CSA C22.2 No. 14-05)US and Canada: The drive is suitable for use on a circuitcapable of delivering not more than 100 kA symmetricalamperes (rms) at 600 V maximum when protected byfuses given in the fuse tableFrequency 50/60 Hz, variation ± 5%, maximum rate of change 17%/sImbalance Max. ± 3% of nominal phase to phase input voltageFundamental power factor(cos phi1 )0.98 (at nominal load)Motor connection dataMotor types Asynchronous AC induction motors, permanent magnetsynchronous motors, AC induction servomotors and ABBsynchronous reluctance motors (SynRM motors)Voltage (U2 ) 0 to U1, 3-phase symmetrical, U max at the field weakeningpointFrequency 0…500 HzFor drives with du/dt filter: 120 HzFor drives with sine filter: 120 HzCurrent See section Ratings.Switching frequency 2.7 kHz (typically)~~~~~~~~