Technical data74Dimensions, weights, noiseSee also the chapter Dimension drawings.Note: The wiring to the I/O options requires some 50 mm (2î) of additional depth.Cooling characteristicsSupply cable fusesFuses for short circuit protection of the supply cable are listed below. The fuses alsoprotect the adjoining equipment of the drive in case of a short circuit. Check that theoperating time of the fuse is below 0.5 seconds. The operating time depends onthe supply network impedance and the cross-sectional area and length of the supplycable. See also chapter Planning the electrical installation.Note: Fuses with a higher current rating must not be used.FramesizeHeight WidthDepth(without optionsinstalled onJCU)Depth(with optionsinstalled onJCU)Weight Noisemm (in.) mm (in.) mm (in.) mm (in.) kg (lbs) dBE 700 (27.56) 313.5 (12.34) 398 (15.67) 415 (16.34) 67 (148) 65Drive typeACSM1-04xxÖPowerloss Air flowMinimum effective areaof air inletMinimum effective areaof air outletIP22 IP54 IP22 IP54W m 3/h ft3 /min cm 2 in 2 cm 2 in 2 cm 2 in 2 cm 2 in 2-110A-4 1060 405 2401000 155 2000 310 1600 250 3200 500-135A-4 1590 405 240-175A-4 2050 405 240-210A-4 2570 405 240Drive typeACSM1-04xxÖInputcurrent(A)IEC fuse UL fuse Cross-sectional area of cableRatedcurrent(A)Voltage(V) ClassRatedcurrent(A)Voltage(V)ULClass mm 2 AWG/MCM-110A-4 107 160 500 gG 150 600 T 95Ö185 3/0 AWGÖ400 MCM-135A-4 131 200 500 gG 200 600 T 95Ö185 3/0 AWGÖ400 MCM-175A-4 171 200 500 gG 225 600 T 95Ö185 3/0 AWGÖ400 MCM-210A-4 205 250 500 gG 300 600 T 95Ö185 3/0 AWGÖ400 MCMPDM-00425726