Planning the electrical installation343ADW000462R0101 DCS880 Hardware Manual e aCross-sectional areas - Tightening torquesRecommended cross-sectional area to DINVDE 0276-1000 and DINVDE 0100-540(PE) trefoil arrangement, up to 50°C ambient temperature.Armature:You will find instructions on how to calculate the PE conductor’s cross-sectional areain VDE 0100 or in equivalent national standards. We would remind you that powerconverters may have a current-limiting effect.Excitation:Converter type C1, D1 U1, V1, W1 PE[Nm]I DC[A-]1[mm²](2.)[mm²]Iv[A~]1[mm²](2.)[mm²] [mm²]DCS880-S0x-0025-xx 25 1 x 6 - 21 1 x 4 - 1x 4 1 x M6 6DCS880-S0x-0050-xx 50 1 x 10 - 41 1 x 6 - 1x 6 1 x M6 6DCS880-S0x-0075-xx 75 1 x 25 - 61 1 x 25 - 1x 16 1 x M6 6DCS880-S0x-0100-xx 100 1 x 25 - 82 1 x 25 - 1x 16 1 x M6 6DCS880-S0x-0150-xx 150 1 x 35 - 114 1 x 35 - 1x 16 1 x M10 25DCS880-S0x-0200-xx 200 2 x 35 1 x 95 163 2 x 25 1 x 95 1x 25 1 x M10 25DCS880-S0x-0250-xx 250 2 x 35 1 x 95 204 2 x 25 1 x 95 1x 25 1 x M10 25DCS880-S0x-0300-xx 300 2 x 70 1 x 95 220 2 x 50 1 x 95 1x 50 1 x M10 25DCS880-S0x-0320-xx 320 2 x 70 1 x 95 220 2 x 50 1 x 95 1x 50 1 x M10 25DCS880-S0x-0350-xx 350 2 x 70 - 286 2 x 50 1x 50 1 x M10 25DCS880-S0x-0450-xx 450 2 x 95 - 367 2 x 95 - 1x 50 1 x M10 25DCS880-S0x-0520-xx 520 2 x 95 - 424 2 x 95 - 1x 50 1 x M10 25DCS880-S0x-0650-xx 650 2 x 120 - 555 2 x 120 - 1x120 1 x M12 50DCS880-S0x-0680-xx 680 2 x 120 - 555 2 x 120 - 1x120 1 x M12 50DCS880-S0x-0820-xx 820 2 x 150 - 669 2 x 120 - 1x120 1 x M12 50DCS880-S0x-1000-xx 1000 2 x 185 - 816 2 x 150 - 1x150 1 x M12 50Size H1 H1 H2 H3, H5, H6 H4 DCF803-0035DC output current 6 A 12 A 18 A 25 A 30 A 35 Amax. cross sectional area 6 mm²/ AWG 10 6 mm²/ AWG 10 6 mm²/ AWG 10 6 mm²/ AWG 10 6 mm²/ AWG 10 6 mm²/ AWG 10min. cross sectional area 1 mm²/ AWG 16 2.5 mm²/ AWG 13 4 mm²/ AWG 11 6 mm²/ AWG 10 6 mm²/ AWG 10 6 mm²/ AWG 10Tightening torque 1.5 ... 1.7 Nm