Technical data493ADW000462R0101 DCS880 Hardware Manual e aCurrent ratings - IEC regenerative** This unit type can be used as large field exciter. Do not forget the SDCS-DSL-H1x (+S199).A 10 % current de-rating is strongly recommended.Sizing: Notes:AC current I AC = 0.82 * IDCThe ratings apply at ambient temperature of 40°C (104°F). For lower temperatures the H6, H7, H8ratings are higher (except Imax).Use DriveSize for detailed dimensioning in case the ambient temperature is below 40°C (104°F)or the drive is loaded cyclically.Standard duty cyclesUnit type I DC I IDC II IDC III IDC IV Size Internalfield current4-Q converters continu-ous100 %15 min150 %60 s100 %15 min150 %120 s100 %15 min200 %10 s400 V / 525 V [A] [A] [A] [A]DCS880-S02-0025-04/05** 25 22 33 21 31 20 40H10.3 ... 6 ADCS880-S02-0050-04/05** 50 38 57 37 55 33 661 ... 12 ADCS880-S02-0075-04/05** 75 60 90 59 88 54 108DCS880-S02-0100-04/05** 100 85 127 83 124 80 160DCS880-S02-0150-04/05 150 114 171 110 165 100 200H2 1 ... 18 ADCS880-S02-0200-04/05** 200 145 217 140 210 115 230DCS880-S02-0250-04/05 250 185 277 180 270 165 330DCS880-S02-0300-04/05 300 225 337 220 330 200 400DCS880-S02-0350-04/05** 350 275 412 265 397 245 490H3 2 ... 25 ADCS880-S02-0450-04/05** 450 350 525 340 510 310 620DCS880-S02-0520-04/05 520 400 600 380 570 350 700DCS880-S02-0680-04/05** 680 525 787 510 765 475 950H4 2 ... 30 ADCS880-S02-0820-04/05 820 630 945 610 915 565 1130DCS880-S02-1000-04/05 1000 750 1125 725 1087 660 1320600 V / 690 VDCS880-S02-0320-06 320 256 384 246 369 235 470 H3 -DCS880-S02-0650-06 650 514 771 508 762 462 924 H4 -100%t150% 100%15 min60 sIDCI150% 100%15 min 120 s10 s200% 100%15 minDZ_LIN_054_duty cycle_a.aitIDCIItIDCIIItIDCIV