4.1.1.2 Function block GUID-EC5F1C83-0F47-4548-86E3-FFE056571241 v2IEC10000287-1-en.vsdI103MEASBLOCKIL1IL2IL3INUL1UL2UL3UL1L2UNPQFIEC10000287 V1 EN-USFigure 5: I103MEAS function block4.1.1.3 SignalsPID-6625-INPUTSIGNALS v4Table 4:I103MEAS Input signalsName Type Default DescriptionBLOCK BOOLEAN 0 Block of service value reportingIL1 REAL 0.0 Service value for current phase L1IL2 REAL 0.0 Service value for current phase L2IL3 REAL 0.0 Service value for current phase L3IN REAL 0.0 Service value for residual current INUL1 REAL 0.0 Service value for voltage phase L1UL2 REAL 0.0 Service value for voltage phase L2UL3 REAL 0.0 Service value for voltage phase L3UL1L2 REAL 0.0 Service value for voltage phase-phase L1-L2UN REAL 0.0 Service value for residual voltage UNP REAL 0.0 Service value for active powerQ REAL 0.0 Service value for reactive powerF REAL 0.0 Service value for system frequency4.1.1.4 SettingsPID-6625-SETTINGS v4Table 5:I103MEAS Non group settings (basic)Name Values (Range) Unit Step Default DescriptionFunctionType 1 - 255 - 1 1 Function type (1-255)MaxIL1 1 - 99999 A 1 3000 Maximum current phase L1MaxIL2 1 - 99999 A 1 3000 Maximum current phase L2MaxIL3 1 - 99999 A 1 3000 Maximum current phase L3Table continues on next pageSection 4 1MRK 511 394-UEN AIEC 60870-5-103 vendor specific implementation24 670 series 2.2 IECCommunication protocol manual