4.1.3.3 SignalsPID-3973-INPUTSIGNALS v5Table 10:I103AR Input signalsName Type Default DescriptionBLOCK BOOLEAN 0 Block of status reporting16_ARACT BOOLEAN 0 Information number 16, auto-recloser active128_CBON BOOLEAN 0 Information number 128, circuit breaker on byauto-recloser130_BLKD BOOLEAN 0 Information number 130, auto-recloser blocked4.1.3.4 SettingsPID-3973-SETTINGS v5Table 11:I103AR Non group settings (basic)Name Values (Range) Unit Step Default DescriptionFunctionType 1 - 255 - 1 1 Function type (1-255)4.1.3.5 Supported information typesAutorecloser indications in monitor direction, I103AR M11874-363 v6Indication block for autorecloser in monitor direction with defined functions.Number of instances: 1Function type is selected with parameter FunctionType.Information number is defined for each output signal.Table 12:I103AR supported indicationsINF Description16 Autorecloser active128 CB on by Autorecloser130 Autorecloser blocked4.1.4 Function status earth-fault for IEC 60870-5-103 I103EFGUID-F23B392E-B55D-4BC3-A0A6-B7992D551092 v14.1.4.1 Functionality GUID-13F90E95-7C8C-4DCB-A9D8-2489B66DB81A v2I103EF is a function block with defined functions for earth fault indications inmonitor direction. This block includes the FunctionType parameter, and theinformation number parameter is defined for each output signal.1MRK 511 394-UEN A Section 4IEC 60870-5-103 vendor specific implementation670 series 2.2 IEC 29Communication protocol manual