4.1.8.3 SignalsPID-6485-INPUTSIGNALS v5Table 25:I103USRDEF Input signalsName Type Default DescriptionBLOCK BOOLEAN 0 Block of status reportingINPUT1 BOOLEAN 0 Binary signal Input 1INPUT2 BOOLEAN 0 Binary signal input 2INPUT3 BOOLEAN 0 Binary signal input 3INPUT4 BOOLEAN 0 Binary signal input 4INPUT5 BOOLEAN 0 Binary signal input 5INPUT6 BOOLEAN 0 Binary signal input 6INPUT7 BOOLEAN 0 Binary signal input 7INPUT8 BOOLEAN 0 Binary signal input 8RT_START BOOLEAN 0 Trig to set base of relative timeGUID-9E29DE39-EA74-4D62-A2BA-F8E31A3D8757 v2RT_START registers the positive transition (0->1) of a pulse and sets the timefrom which relative time is derived. Relative time is assigned only to inputs wherethe corresponding TypNo parameter is set to Relative. The maximum relative timeand unit conform to the IEC 60870-5-103 standard.4.1.8.4 SettingsPID-6485-SETTINGS v5Table 26:I103USRDEF Non group settings (basic)Name Values (Range) Unit Step Default DescriptionFunctionType 1 - 255 - 1 5 Function type (1-255)InfNo1 1 - 255 - 1 1 Information number for binary input 1(1-255)InfNo2 1 - 255 - 1 2 Information number for binary input 2(1-255)InfNo3 1 - 255 - 1 3 Information number for binary input 3(1-255)InfNo4 1 - 255 - 1 4 Information number for binary input 4(1-255)InfNo5 1 - 255 - 1 5 Information number for binary input 5(1-255)InfNo6 1 - 255 - 1 6 Information number for binary input 6(1-255)InfNo7 1 - 255 - 1 7 Information number for binary input 7(1-255)InfNo8 1 - 255 - 1 8 Information number for binary input 8(1-255)TypNo1 AbsoluteRelative- - Absolute Type identification (TYP)Table continues on next pageSection 4 1MRK 511 394-UEN AIEC 60870-5-103 vendor specific implementation38 670 series 2.2 IECCommunication protocol manual