Name Type Values (Range) Unit DescriptionAI_RANGE5 Enum 0=normal1=high2=low3=high-high4=low-lowRTD input, Connectors9-10-11c, rangeAI_DB6 FLOAT32 -10000.0...10000.0RTD input, Connectors13-14-12c, reportedvalueAI_RANGE6 Enum 0=normal1=high2=low3=high-high4=low-lowRTD input, Connectors13-14-12c, rangeAI_DB7 FLOAT32 -10000.0...10000.0RTD input, Connectors15-16-12c, reportedvalueAI_RANGE7 Enum 0=normal1=high2=low3=high-high4=low-lowRTD input, Connectors15-16-12c, rangeAI_DB8 FLOAT32 -10000.0...10000.0RTD input, Connectors17-18-12c, reportedvalueAI_RANGE8 Enum 0=normal1=high2=low3=high-high4=low-lowRTD input, Connectors17-18-12c, range3.13 SMV function blocksSMV function blocks are used in the process bus applications with the sending of thesampled values of analog currents and voltages and with the receiving of the sampledvalues of voltages.3.13.1 IEC 61850-9-2 LE sampled values sending SMVSENDER3.13.1.1 FunctionalityThe SMVSENDER function block is used for activating the SMV sendingfunctionality. It adds/removes the sampled value control block and the related data setinto/from the sending device's configuration. It has no input or output signals.SMVSENDER can be disabled with the Operation setting value “off”. If theSMVSENDER is disabled from the LHMI, it can only be enabled from the LHMI.When disabled, the sending of the samples values is disabled.1MRS758755 A Section 3Basic functionsREC615 and RER615 101Technical Manual