Each control point or SPCRGAPC can only be accessed remotely throughcommunication. SPCRGAPC follows the local or remote (L/R) state if the setting LocRem restriction is "true". If the Loc Rem restriction setting is "false", local or remote(L/R) state is ignored, that is, all controls are allowed regardless of the local or remotestate.The BLOCK input can be used for blocking the output functionality. The BLOCK inputoperation depends on the Operation mode setting. If the Operation mode setting is setto "Toggle", the output state cannot be changed when the input BLOCK is TRUE. If theOperation mode setting is set to "Pulsed", the activation of the BLOCK input resets theoutput to the FALSE state.3.16.13.4 SignalsTable 179:SPCRGAPC Input signalsName Type Default DescriptionBLOCK BOOLEAN 0=False Block signal for activating the blocking modeTable 180:SPCRGAPC Output signalsName Type DescriptionO1 BOOLEAN Output 1 statusO2 BOOLEAN Output 2 statusO3 BOOLEAN Output 3 statusO4 BOOLEAN Output 4 statusO5 BOOLEAN Output 5 statusO6 BOOLEAN Output 6 statusO7 BOOLEAN Output 7 statusO8 BOOLEAN Output 8 statusO9 BOOLEAN Output 9 statusO10 BOOLEAN Output 10 statusO11 BOOLEAN Output 11 statusO12 BOOLEAN Output 12 statusO13 BOOLEAN Output 13 statusO14 BOOLEAN Output 14 statusO15 BOOLEAN Output 15 statusO16 BOOLEAN Output 16 statusSection 3 1MRS758755 ABasic functions168 REC615 and RER615Technical Manual