Parameter Values (Range) Unit Step Default DescriptionOperation mode 0=Pulsed1=Persistent-1=Off-1=Off Operation mode for generic control pointPulse length 10...3600000 ms 10 1000 Pulse length for pulsed operation modeDescription SPCLGAPC1Output 16Generic control point description3.16.15 Programmable buttons (4 buttons) FKEY4GGIO3.16.15.1 IdentificationFunction description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberProgrammable buttons (4 buttons) FKEY4GGIO FKEY4GGIO FKEY4GGIO3.16.15.2 Function blockFKEY4GGIOK2K1K3K4L2L1L3L4GUID-6DBCE16B-0F2A-4C0C-BBAC-0293D9E1EB8B V1 ENFigure 106: Function block3.16.15.3 FunctionalityThe Programmable buttons function FKEY4GGIO is a simple interface between thepanel and the application. The user input from the buttons available on the front panelis transferred to the assigned functionality and the corresponding LED is turned ONor OFF for indication. The behavior of each function key in the specific application isconfigured by connection with other application functions. This gives maximumflexibility.3.16.15.4 Operation principleInputs L1...L4 represent the LEDs on the relay's LHMI. When an input is set toTRUE, the corresponding LED is lit. When a function key on the LHMI is pressed, thecorresponding output K1...K4 is set to TRUE.Each function key has settable text descriptions for the on and off states. The visibilityof function key text descriptions on the LHMI can be selected with setting parameterFunction key text visibility.1MRS758755 A Section 3Basic functionsREC615 and RER615 175Technical Manual