Contents - Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Section 1 Introduction
- Product documentation
- Document revision history
- Related documents
- Document conventions
- IEC 61850 edition 1 / edition 2 mapping
- Section 2 Application
- Main protection functions
- Back-up protection functions
- Control and monitoring functions
- Communication
- Basic IED functions
- Section 3 Configuration
- Description of A05
- Section 4 Analog inputs
- Setting of the phase reference channel
- Example 2
- Example 3
- Examples on how to connect, configure and set CT inputs for most commonly used CT connections
- Example on how to connect a star connected three phase CT set to the IED
- Example how to connect single-phase CT to the IED
- Relationships between setting parameter Base Current, CT rated primary current and minimum pickup of a protection IED
- Examples how to connect, configure and set VT inputs for most commonly used VT connections
- Examples on how to connect a three phase-to-earth connected VT to the IED
- Example on how to connect a phase-to-phase connected VT to the IED
- Example on how to connect an open delta VT to the IED for high impedance earthed or unearthed networks
- for low impedance earthed or solidly earthed power systems
- Section 5 Local HMI
- Display
- LEDs
- Keypad
- Local HMI functionality
- Parameter management
- Front communication
- Transformer differential protection T2WPDIF and T3WPDIF
- Setting guidelines
- Elimination of zero sequence currents
- Inrush restraint methods
- Cross-blocking between phases
- Differential current alarm
- Switch onto fault feature
- protection
- Application Examples
- Summary and conclusions
- Low impedance restricted earth fault protection REFPDIF
- Transformer winding, solidly earthed
- Autotransformer winding, solidly earthed
- Reactor winding, solidly earthed
- Multi-breaker applications
- CT earthing direction
- Settings
- Instantaneous phase overcurrent protection PHPIOC
- Meshed network with parallel line
- Directional phase overcurrent protection, four steps OC4PTOC
- Settings for each step
- Setting example
- Instantaneous residual overcurrent protection EFPIOC
- Directional residual overcurrent protection, four steps EF4PTOC
- Common settings for all steps
- nd harmonic restrain
- Parallel transformer inrush current logic
- Switch onto fault logic
- Settings for each step (x = 1, 2, 3 and 4)
- Transformer application example
- Thermal overload protection, two time constants TRPTTR
- Setting guideline
- Breaker failure protection CCRBRF
- Application
- Pole discordance protection CCPDSC
- Identification
- Two step undervoltage protection UV2PTUV
- Settings for two step undervoltage protection
- Two step overvoltage protection OV2PTOV
- Equipment protection, such as for motors, generators reactors and transformers
- Two step residual overvoltage protection ROV2PTOV
- reactors and transformersEquipment protection for transformers
- Direct earthed system
- Settings for two step residual overvoltage protection
- Overexcitation protection OEXPVPH
- Service value report
- Underfrequency protection SAPTUF
- Overfrequency protection SAPTOF
- Rate-of-change of frequency protection SAPFRC
- Current circuit supervision CCSSPVC
- Fuse failure supervision FUFSPVC
- Negative sequence based
- Zero sequence based
- Dead line detection
- Section 11 Control
- Bay control QCBAY
- Switch controller SCSWI
- Switches SXCBR
- XLNPROXY
- Interaction between modules
- Bay control (QCBAY)
- Switch (SXCBR)
- TR1ATCC or TR8ATCC Setting group
- TCMYLTC and TCLYLTC general settings
- Logic rotating switch for function selection and LHMI presentation SLGAPC
- Selector mini switch VSGAPC
- Tripping logic SMPPTRC
- Three-phase tripping
- Single-, two- or three-phase tripping
- Example of directional data
- Blocking of the function block
- Fixed signal function block FXDSIGN
- Boolean 16 to Integer conversion B16I
- Boolean to integer conversion with logical node representation, 16 bit BTIGAPC
- Integer to Boolean 16 conversion IB16
- representation ITBGAPC
- Elapsed time integrator with limit transgression and overflow supervision TEIGAPC
- Comparator for real inputs - REALCOMP
- Measurement
- Zero clamping
- Setting examples
- Gas medium supervision SSIMG
- Liquid medium supervision SSIML
- Breaker monitoring SSCBR
- Event function EVENT
- Recording times
- Binary input signals
- Consideration
- Logical signal status report BINSTATREP
- Pulse-counter logic PCFCNT
- Function for energy calculation and demand handling ETPMMTR
- Access point
- Redundant communication
- Merging unit
- Communication protocols
- Receiving data
- IEC/UCA 61850-9-2LE communication protocol
- Specific settings related to the IEC/UCA 61850-9-2LE communication
- Setting examples for IEC/UCA 61850-9-2LE and time synchronization
- IEC 61850 quality expander QUALEXP
- LON communication protocol
- MULTICMDRCV and MULTICMDSND
- IEC 60870-5-103 communication protocol
- Design
- Settings for RS485 and optical serial communication
- Settings from PCM600
- Function and information types
- DNP3 Communication protocol
- Authority status ATHSTAT
- Change lock CHNGLCK
- Denial of service SCHLCCH/RCHLCCH
- IED identifiers TERMINALID
- Measured value expander block RANGE_XP
- Signal matrix for binary inputs SMBI
- Signal matrix for analog inputs SMAI
- Test mode functionality TESTMODE
- Synchronization
- Process bus IEC/UCA 61850-9-2LE synchronization
- Current transformer requirements
- Conditions
- Fault current
- General current transformer requirements
- Distance protection
- Breaker failure protection
- Current transformer requirements for CTs according to other standards
- Current transformers according to ANSI/IEEE
- SNTP server requirements
- Section 20 Glossary
|
Application................................................................................. 258Integer to Boolean 16 conversion IB16.......................................... 259Identification.............................................................................. 259Application................................................................................. 259Integer to Boolean 16 conversion with logic noderepresentation ITBGAPC................................................................260Identification.............................................................................. 260Application................................................................................. 260Elapsed time integrator with limit transgression and overflowsupervision TEIGAPC.....................................................................261Identification.............................................................................. 261Application................................................................................. 262Setting guidelines...................................................................... 262Comparator for integer inputs - INTCOMP..................................... 262Identification.............................................................................. 262Application................................................................................. 263Setting guidelines...................................................................... 263Setting example.........................................................................263Comparator for real inputs - REALCOMP...................................... 264Identification.............................................................................. 264Application................................................................................. 264Setting guidelines...................................................................... 264Setting example.........................................................................265Section 13 Monitoring.....................................................................267Measurement..................................................................................267Identification.............................................................................. 267Application................................................................................. 267Zero clamping............................................................................269Setting guidelines...................................................................... 270Setting examples..................................................................272Gas medium supervision SSIMG................................................... 277Identification.............................................................................. 277Application................................................................................. 277Setting guidelines...................................................................... 278Liquid medium supervision SSIML................................................. 279Identification.............................................................................. 279Application................................................................................. 279Setting guidelines...................................................................... 279Breaker monitoring SSCBR............................................................280Identification.............................................................................. 280Application................................................................................. 280Setting guidelines...................................................................... 283Setting procedure on the IED............................................... 283Table of contents8 Transformer protection RET650 2.2 IECApplication manual PreviousNext |