Name of input Type Default Description Value whenactivatedValue whendeactivatedIN1 BOOLEAN 0 Input 1 1 0IN2 BOOLEAN 0 Input 2 2 0IN3 BOOLEAN 0 Input 3 4 0IN4 BOOLEAN 0 Input 4 8 0IN5 BOOLEAN 0 Input 5 16 0IN6 BOOLEAN 0 Input 6 32 0IN7 BOOLEAN 0 Input 7 64 0IN8 BOOLEAN 0 Input 8 128 0IN9 BOOLEAN 0 Input 9 256 0IN10 BOOLEAN 0 Input 10 512 0IN11 BOOLEAN 0 Input 11 1024 0IN12 BOOLEAN 0 Input 12 2048 0IN13 BOOLEAN 0 Input 13 4096 0IN14 BOOLEAN 0 Input 14 8192 0IN15 BOOLEAN 0 Input 15 16384 0IN16 BOOLEAN 0 Input 16 32768 0The sum of the numbers in column “Value when activated” when all INx (where1≤x≤16) are active that is=1; is 65535. 65535 is the highest boolean value that canbe converted to an integer by the IB16 function block.12.11 Integer to Boolean 16 conversion with logic noderepresentation ITBGAPC SEMOD158419-1 v312.11.1 IdentificationSEMOD167944-2 v4Function description IEC 61850identificationANSI/IEEE C37.2device numberInteger to boolean 16 conversion withlogic node representationITBGAPC - -12.11.2 Application SEMOD158512-5 v7Integer to boolean 16 conversion with logic node representation function(ITBGAPC) is used to transform an integer into a set of 16 boolean signals.ITBGAPC function can receive an integer from a station computer – for example,over IEC 61850–8–1. This function is very useful when the user wants to generateSection 12 1MRK 504 169-UEN ALogic260 Transformer protection RET650 2.2 IECApplication manual