16.6.2.1 Settings for RS485 and optical serial communication M17109-118 v12General settingsSPA, DNP and IEC 60870-5-103 can be configured to operate on the SLM opticalserial port while DNP and IEC 60870-5-103 additionally can utilize the RS485port. A single protocol can be active on a given physical port at any time.Two different areas in the HMI are used to configure the IEC 60870-5-103protocol.1. The port specific IEC 60870-5-103 protocol parameters are configured under:Main menu/Configuration/Communication/Station Communication/IEC60870-5-103/• • SlaveAddress• BaudRate• RevPolarity (optical channel only)• CycMeasRepTime• MasterTimeDomain• TimeSyncMode• EvalTimeAccuracy• EventRepMode• CmdMode• RepIntermediatePos is:• “OPTICAL103:1” for the optical serial channel on the SLM• “RS485103:1” for the RS485 port2. The protocol to activate on a physical port is selected under:Main menu/Configuration/Communication/Station Communication/Portconfiguration/• RS485 port• RS485PROT:1 (off, DNP, IEC103)• SLM optical serial port• PROTOCOL:1 (off, DNP, IEC103, SPA)Section 16 1MRK 504 169-UEN AStation communication332 Transformer protection RET650 2.2 IECApplication manual