12.9 Boolean to integer conversion with logical noderepresentation, 16 bit BTIGAPC SEMOD175753-1 v412.9.1 IdentificationSEMOD175757-2 v5Function description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberBoolean to integer conversion withlogical node representation, 16 bitBTIGAPC - -12.9.2 Application SEMOD175849-4 v6Boolean to integer conversion with logical node representation, 16 bit (BTIGAPC)is used to transform a set of 16 binary (logical) signals into an integer. BTIGAPChas a logical node mapping in IEC 61850.The BTIGAPC function will transfer a combination of up to 16 binary inputs INxwhere 1≤x≤16 to an integer. Each INx represents a value according to the tablebelow from 0 to 32768. This follows the general formula: INx = 2x-1 where1≤x≤16. The sum of all the values on the activated INx will be available on theoutput OUT as a sum of the values of all the inputs INx that are activated. OUT isan integer. When all INx where 1≤x≤16 are activated that is = Boolean 1 itcorresponds to that integer 65535 is available on the output OUT. BTIGAPCfunction is designed for receiving up to 16 booleans input locally. If the BLOCKinput is activated, it will freeze the output at the last value.Values of each of the different OUTx from function block BTIGAPC for 1≤x≤16.The sum of the value on each INx corresponds to the integer presented on theoutput OUT on the function block BTIGAPC.Name of input Type Default Description Value whenactivatedValue whendeactivatedIN1 BOOLEAN 0 Input 1 1 0IN2 BOOLEAN 0 Input 2 2 0IN3 BOOLEAN 0 Input 3 4 0IN4 BOOLEAN 0 Input 4 8 0IN5 BOOLEAN 0 Input 5 16 0IN6 BOOLEAN 0 Input 6 32 0IN7 BOOLEAN 0 Input 7 64 0IN8 BOOLEAN 0 Input 8 128 0IN9 BOOLEAN 0 Input 9 256 0IN10 BOOLEAN 0 Input 10 512 0Table continues on next pageSection 12 1MRK 504 169-UEN ALogic258 Transformer protection RET650 2.2 IECApplication manual