16.2.2 Setting guidelines SEMOD55317-5 v7There are two settings related to the IEC 61850–8–1 protocol:Operation: User can set IEC 61850 communication to On or Off.GOOSEPortEd1: Selection of the Ethernet link where GOOSE traffic shall be sentand received. This is only valid for Edition 1 and can be ignored if Edition 2 isused. For Edition 2, the Ethernet link selection is done with the EthernetConfiguration Tool (ECT) in PCM600.16.2.3 Horizontal communication via GOOSE16.2.3.1 Sending data GUID-9888ECAD-8221-4B31-A443-EB1E3A9022C4 v1In addition to the data object and data attributes of the logical nodes, it is possibleto send the outputs of the function blocks using the generic communication blocks.The outputs of this function can be set in a dataset and be sent in a GOOSE ControlBlock to other subscriber IEDs. There are different function blocks for differenttype of sending data.Generic communication function for Single Point indication SPGAPC,SP16GAPC SEMOD55999-1 v4Application SEMOD55350-5 v8Generic communication function for Single Point Value (SPGAPC) function isused to send one single logical output to other systems or equipment in thesubstation. SP16GAPC can be used to send up to 16 single point values from theapplication functions running in the same cycle time. SPGAPC has one visibleinput and SPGAPC16 has 16 visible inputs that should be connected in the ACTtool.Setting guidelines SEMOD55376-5 v5There are no settings available for the user for SPGAPC.Generic communication function for Measured Value MVGAPCSEMOD55402-1 v3Application SEMOD55872-5 v10Generic communication function for measured values (MVGAPC) function is usedto send the instantaneous value of an analog signal to other systems or equipmentin the substation. It can also be used inside the same IED, to attach a RANGEaspect to an analog value and to permit measurement supervision on that value.Setting guidelines SEMOD55424-5 v5The settings available for Generic communication function for Measured Value(MVGAPC) function allows the user to choose a deadband and a zero deadband forthe monitored signal. Values within the zero deadband are considered as zero.1MRK 504 169-UEN A Section 16Station communicationTransformer protection RET650 2.2 IEC 307Application manual