en_BA_OxE7_PosCon3D.docx 41/64 Baumer Electric AG17.07.2014 14:21/tof V1.01 ANW_81125407 Frauenfeld, Switzerland5.9.3 LIMIT LEFTValue measured horizontally from reference point (0 mm), to the left.All edges to the left of this range are suppressed.5.9.4 LIMIT RIGHTValue measured horizontally from reference point (0 mm), to the right.All edges to the right of this range are suppressed.5.9.5 OFFSETAll edges below this line are suppressed.In case of standard installation, if FLEX MOUNT is not activated, the offset is measured from the sensorreference point (250 mm away from the sensor).If FLEX MOUNT is activated, the taught-in reference surface is 0.TEACH REF activatedIf the FLEX MOUNT function is activated,the sensor already knows the reference surface;the desired offset value can be entereddirectly.ExampleThe offset should be 10 mm above the taught-inreference surface.Displayed value in the OFFSET menu: 0 mm. Entered OFFSET = 10 mm10 mm10 mm10 mm; offsetTaught-inreference surface Reference surfaceReferencepoint250 mmStandard installationIn standard installation, the distance between thereference point and the sensor is always 250 mm.The distance from the reference surface can beoutput with LIVE MONITOR, which makes it easier tocalculate the offset.ExampleThe offset should be 10 mm above the referencesurface.Displayed value in LIVE DIAGNOSIS: 240 mm.250 mm - 240 mm + 10 mm = 20 mm Entered OFFSET = 20 mm240 mm