INSTALLATION3-2Figure 3-1. Attaching the Strain Relief Bracket3.3 INSTALLING THE MicroMMAC-TThe MicroMMAC-T can be rack-mounted, wall-mounted, or placed onany horizontal surface. Refer to the following subsections for theappropriate installation instructions. When installing the MicroMMAC-Tinto something other than a 19-inch rack, installation requires thefollowing:• An unrestricted free surface area at least 21 inches wide, 18 inchesdeep, and 6 inches high.• A single phase 85 to 264 Vac, 15A, grounded power receptacle locatedwithin 7 feet of the site.• If a shelving unit is used, it must be able to support 30 pounds of staticweight.• The temperature in selected location must be between 5° and 50°C,and change less than 10°C per hour.NOTE: Be sure that the selected location is within reach of the networkcabling.3.3.1 Rack-Mounting the MicroMMAC-TRefer to Figure 3-2 and perform the following steps to install theMicroMMAC-T in a 19-inch rack:1. Remove the four cover screws located along the front edges of eachside of the MicroMMAC-T.TOKEN RING HUB WITH LANVIEW®SUPPORTING 100 OHM STP CABLEMicroMMAC-24T