– 24 –7-2. Operation DataNOTES :1. Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bent.(Thermistor themometer)2. Connecting piping condition : 5 mModel name Standard Indoor Outdoor Compressorpressure fan mode fan mode revolutionIndoor Outdoor P (MPa) T1 (°C) T2 (°C) (rps)27/19 35/- 42NQV025H 0.9 to 1.1 12 to 14 37 to 39 High High 4942NQV035M 0.8 to 1.0 11 to 13 39 to 41 High High 7742NQV035H 0.8 to 1.0 11 to 13 46 to 48 High High 6342NQV045M 0.7 to 0.9 10 to 12 47 to 49 High High 8942NQV045H 0.8 to 1.0 11 to 13 40 to 42 High High 83condition(°C)Tempeature Heat exchangerpipe temp.Model name Standard Indoor Outdoor CompressorRAS- pressure fan mode fan mode revolutionIndoor Outdoor P (MPa) T1 (°C) T2 (°C) (rps)20/- 7/6 42NQV025H 2.5 to 2.7 39 to 41 0 to 3 High High 6042NQV035M 2.7 to 2.9 43 to 45 0 to 2 High High 8042NQV035H 2.6 to 2.8 41 to 43 0 to 2 High High 6642NQV045M 2.5 to 2.7 39 to 41 0 to 2 High High 8942NQV045H 2.7 to 2.9 43 to 45 0 to 2 High High 83Tempeature Heat exchangercondition(°C) pipe temp.FILE NO. SVM-07013