– 64 –Packed Valve handling precautions• Open the valve stem all the way; but do not try toopen it beyond the stopper.• Securely tighten the valve stem cap with torque inthe following table:Hexagonal wrench is required.Fig. 10-4-1010-4-5. Wiring Connection1. Remove the valve cover, the electric parts coverand the cord clamp from the outdoor unit.2. Connect the connecting cable to the terminal asidentified by the matching numbers on theterminal block of indoor and outdoor unit.3. Insert the power cord and the connecting cablefully into the terminal block and secure it tightlywith screws.4. Insulate the unused cords (conductors) fromwater entering in the outdoor unit. Locate themso that they do not touch any electrical or metalparts.5. Secure the power cord and the connecting cablewith the cord clamp.6. Attach the electric parts cover and the valvecover on the outdoor unit.Stripping length of connecting cableFig. 10-4-11Fig. 10-4-124mmCAUTION• Incorrect wiring connection may cause electri-cal parts to burn out.• Be sure to comply with local regulations/codeswhen running the wire from outdoor unit toindoor unit.(Size of wire and wiring method etc.)• Every wire must be securely connected.• If incorrect or incomplete wiring is carried out,fire or smoke may result.• Prepare the power supply for the exclusive useof the air conditioner.• This product can be connected to the mainbreaker.Connection to fixed wiring:A switch which disconnects all poles and has acontact separation of at least 3 mm must beincorporated in the fixed wiring when connect-ing to a main breaker circuit.Gas side (Ø12.7 mm)Gas side (Ø9.52 mm)Liquid side (Ø6.35 mm)Service port50 to 62 N•m (5.0 to 6.2 kgf•m)33 to 42 N•m (3.3 to 4.2 kgf•m)14 to 18 N•m (1.4 to 1.8 kgf•m)14 to 18 N•m (1.4 to 1.8 kgf•m)Model RAS-Power sourceMaximum runningcurrentInstallation fuseratingPower cordConnection cable220 – 240 V ~50 Hz8.5 A16 A breaker or fuse(All types can be used.)H07RN-F or 245IEC66 (1.5 mm²)H07RN-F or 245IEC66 (1.0 mm²)Revised13.0 A38NYV025H38NYV035M38NYV035H38NYV045M 38NYV045HFILE NO. SVM-07013Terminal blockPower cordConnecting cableConnecting cable Power cord0101010130 3040 40L N1 2 3Earth lineEarth line