– 60 –CAUTION• Bind the auxiliary pipes (two) and connectingcable with facing tape tightly.In case of leftward piping and rear-leftwardpiping, bind the auxiliary pipes (two) only withfacing tape.Fig. 10-3-18• Carefully arrange the pipes so that none of thepipes stick out of the rear plate of the indoor unit.• Carefully connect the auxiliary pipes andconnecting pipes to each other and cut off theinsulating tape wound on the connecting pipeto avoid double-taping at the joint, moreover,seal the joint with the vinyl tape, etc.• Since condensation can result in machineperformance trouble, be sure to insulate bothconnecting pipes. (Use polyethylene foam asinsulating material.)• When bending a pipe, be careful not to crush it.10-3-6. Indoor Unit Installation1. Pass the pipe through the hole in the wall, andhook the indoor unit on the installation plate atthe upper hooks.2. Swing the indoor unit to right and left to confirmthat it is firmly hooked on the installation plate.3. While pressing the indoor unit onto the wall, hookit at the lower part on the installation plate.Pull the indoor unit toward you to confirm that it isfirmly hooked on the installation plate.InstallationplateIndoor unitConnectingcableAuxiliary pipes10-3-7. Drainage1. Run the drain hose at a downward sloped angle.NOTE :• Hole should be made at a slight downward slanton the outdoor side.Fig. 10-3-212. Put water in the drain pan and make sure that thewater is being drained outside.3. When connecting extension drain hose, insulatethe connection part of extension drain hose withshield pipe.Fig. 10-3-22CAUTIONInstall the drain pipe for proper drainage.Improper drainage can result in water drippinginside the room.This air conditioner has been designed to drainwater collected from condensation which forms onthe back of the indoor unit, to the drain pan.Therefore, do not locate the power cord and otherparts at a high place than the drain guide.Fig. 10-3-19• For detaching the indoor unit from the installationplate pull the indoor unit toward you while pushingthe bottom up at the specified places.Fig. 10-3-20PushPushPush (unhook)1 InstallationplateHook here2Hook150 mmor moreDo not rise the drain hose. Do not form the drain hoseinto the waved shape.Do not put thedrain hose endinto water.Do not put the drainhose end in thedrainage ditch.Shield pipeExtension drain hoseInside the roomDrain hoseSpace forpipesWallDrainguideFig. 10-3-23FILE NO. SVM-07013