39Table 10 — Menu Structure* (cont)MENU PARAMETERPARAMETERDEFAULTVALUEPARAMETERRANGE ANDINCREMENT† NOTESADVANCEDSETUP (CONT)MAT T CAL 0.0°F ±2.5 F SUPPLY AIR TEMPERATURE CALIBRATIONAllows for the operator to adjust for an out of calibration temperature sensor.OAS T CAL 0.0°F ±2.5 F OUTSIDE AIR TEMPERATURE CALIBRATIONAllows for the operator to adjust for an out of calibration temperature sensor.OA H CAL 0% RH ±10% RH OUTSIDE AIR HUMIDITY CALIBRATIONAllows for operator to adjust for an out of calibration humidity sensor.RA T CAL 0.0°F ±2.5 F RETURN AIR TEMPERATURE CALIBRATIONAllows for the operator to adjust for an out of calibration temperature sensor.RA H CAL 0% RH ±10% RH RETURN AIR HUMIDITY CALIBRATIONAllows for operator to adjust for an out of calibration humidity sensor.DA T CAL 0.0°F ±2.5 F DISCHARGE AIR TEMPERATURE CALIBRATIONAllows for the operator to adjust for an out of calibration temperature sensor.2SP FAN DELAY 5 Minutes 0 to 20 minutes in 1minute incrementsTIME DELAY ON SECOND STAGE ECONOMIZINGWhen in economizing mode this is the delay for the high speed fan to try to sat-isfy the call for second stage cooling before the first stage mechanical coolingis enabled.CHECKOUTDAMPER MINIMUMPOSITIONN/A N/A The checkout for the damper minimum position is based on the system.DAMPER OPEN N/A N/A Position damper to the full open position.Exhaust fan contacts enable during the DAMPER OPEN test. Make sure youpause in the mode to allow exhaust contacts to energize due to the delay inthe system.DAMPER CLOSE N/A N/A Positions damper to the fully closed positionCONNECT Y1–O N/A N/A Closes the Y1-O relay (Y1-O)CONNECT Y2–O N/A N/A Closes the Y2-O relay (Y2-O)CONNECT AUX1-O N/A N/A Energizes the AUX output. If Aux setting is:• NONE — not action taken• ERV — 24 Vac out. Turns on or signals an ERV that the conditions are notgood for economizing but are for ERV operation. ††• SYS — 24 Vac out. Issues a system alarmCONNECT EXH1 N/A N/A Closes the power exhaust fan 2 relay (EXH1)ALARMSAlarms display only when they are active. The menu title “ALARMS(#)” includes the number of active alarms in parenthesis ( ). When using SYLK bussensors, “SYLK” will appear on the screen, and when using 20k OA temperature sensors, “SENS T” will appear on the screenMA T SENS ERR N/A N/A SUPPLY AIR TEMPERATURE SENSOR ERRORMixed air sensor has failed or become disconnected - check wiring thenreplace sensor if the alarm continues.CO2 SENS ERR N/A N/A CO 2 SENSOR ERRORCO 2 sensor has failed, gone out of range or become disconnected - check wir-ing then replace sensor if the alarm continues.OA SYLK T ERR N/A N/A OUTSIDE AIR S-BUS SENSOR ERROROutdoor air enthalpy sensor has failed or become disconnected - check wiringthen replace sensor if the alarm continues.OA SYLK H ERR N/A N/ARA SYLK T ERR N/A N/A RETURN AIR S-BUS SENSOR ERRORReturn air enthalpy sensor has failed or become disconnected - check wiringthen replace sensor if the alarm continues.RA SYLK H ERR N/A N/ADA SYLK T ERR N/A N/A DISCHARGE AIR S-BUS SENSOR ERRORDischarge air sensor has failed or become disconnected - check wiring thenreplace sensor if the alarm continues.OA SENS T ERR N/A N/A OUTSIDE AIR TEMPERATURE SENSOR ERROROutdoor air temperature sensor has failed or become disconnected - checkwiring then replace if the alarm continues.ACT ERROR N/A N/A ACTUATOR ERRORActuator has failed or become disconnected - check for stall, over voltage,under voltage and actuator count. Replace actuator if damper is movable andsupply voltage is between 21.6 V and 26.4 V. Check actuator count on STA-TUS menu.FREEZE ALARM N/A N/A Check if outdoor temperature is below the LOW Temp Lockout on setpointmenu. Check if Mixed air temperature on STATUS menu is below the Lo Set-point on Advanced menu. When conditions are back in normal range then thealarm will go away.