454. Press the (Menu Up/Exit) button to complete the actionand return to the previous menu.NOTE: If the alarm still exists after clearing it, it is redisplayedwithin 5 seconds.SMOKE DETECTORSSmoke detectors are available as factory-installed options on50HCQ models. Smoke detectors may be specified for SupplyAir only or for Return Air without or with economizer, or incombination of Supply Air and Return Air. Return Air smokedetectors are arranged for vertical return configurations only. Allcomponents necessary for operation are factory-provided andmounted. The unit is factory-configured for immediate smokedetector shutdown operation; additional wiring or modificationsto unit terminal board may be necessary to complete the unit andsmoke detector configuration to meet project requirements.Units equipped with factory-optional Return Air smoke detec-tors require a relocation of the sensor module at unit installa-tion. See Fig. 51 for the as-shipped location.Completing Return Air Smoke Sensor Installation1. Unscrew the two screws holding the Return Air SmokeDetector assembly. See Fig. 52, Step 1. Save the screws.2. Turn the assembly 90 degrees and then rotate end to end.Make sure that the elbow fitting is pointing down. See Fig.52, Step 2.3. Screw the sensor and detector plate into its operating posi-tion using screws from Step 1. See Fig. 52, Step 3.4. Connect the flexible tube on the sampling inlet to the sam-pling tube on the basepan.Fig. 51 — Return Air Smoke Detector,Shipping PositionAdditional Application DataRefer to the application data document “Factory InstalledSmoke Detectors for Small and Medium Rooftop Units 2 to 25Tons” for discussions on additional control features of thesesmoke detectors including multiple unit coordination.RTU OPEN CONTROLLER (FACTORY OPTION)For details on operating 50HCQ units equipped with the facto-ry-installed RTU Open controller option, refer to the Factory-Installed Option RTU Open Multi-Protocol Controller Con-trols, Start-Up, Operation and Troubleshooting manual.CONTROLLER OPTIONSLow AmbientIf the unit comes with Electro-Mechanical (EM) control, thenno adjustment is necessary.If the unit comes with the RTU Open control option, then referto its installation control manual for details on adjusting “Cool-ing Lock-Out” setting and configure for the specific job re-quirements.Step 12 — Adjust Factory-Installed OptionsSMOKE DETECTORSSmoke detector(s) will be connected at the Controls Connec-tions Board, at terminals marked “Smoke Shutdown.” Cutjumper JMP 3 when ready to energize unit.ECONOMI$ER IV OCCUPANCY SWITCHSee Fig. 53 for general EconoMi$er IV wiring. External occu-pancy control is managed through a connection on the ControlsConnections Board.If external occupancy control is desired, connect a time clockor remotely controlled switch (closed for Occupied, open forUnoccupied sequence) at terminals marked OCCUPANCY.Cut jumper JMP 2 to complete the installation.Step 13 — Install AccessoriesAvailable accessories include:• Roof curb• Thru-base connection kit (must be installed before unit isset on curb)• Electric heaters and single-point connection kits• Manual outside air damper• Two-position motorized outside air damper• EconoMi$er ® IV (with control)• EconoMi$er2 (without control/for external signal)• Power Exhaust• Differential dry-bulb sensor (EconoMi$er IV)• Outdoor enthalpy sensor• Differential enthalpy sensor• CO 2 sensor• Smoke Detector (Return Air and/or Supply Air)• Louvered hail guard• Motormaster ® head pressure controls• Phase monitor controlRefer to separate installation instructions for information on in-stalling these accessories.RETURN AIRSMOKE DETECTOR(AS SHIPPED)