34terminal for connecting to the controller. Each sensor hasfour LEDs (for Power, Trouble, Alarm and Dirty) and amanual test/reset button (on the left--side of the housing).Duct smoke sensorcontrollerFastener(2X)Controller coverConduit nuts(supplied by installer)Conduit support plateCover gasket(ordering option)Conduit couplings(supplied by installer)Terminal block coverController housingand electronicsAlarm PowerTest/resetswitchTroubleC08208Fig. 58 -- Controller AssemblyAir is introduced to the duct smoke detector sensor’ssensing chamber through a sampling tube that extends intothe HVAC duct and is directed back into the ventilationsystem through a (shorter) exhaust tube. The difference inair pressure between the two tubes pulls the sampled airthrough the sensing chamber. When a sufficient amount ofsmoke is detected in the sensing chamber, the sensorsignals an alarm state and the controller automaticallytakes the appropriate action to shut down fans andblowers, change over air handling systems, notify the firealarm control panel, etc.The sensor uses a process called differential sensing toprevent gradual environmental changes from triggeringfalse alarms. A rapid change in environmental conditions,such as smoke from a fire, causes the sensor to signal analarm state but dust and debris accumulated over timedoes not.For installations using two sensors, the duct smokedetector does not differentiate which sensor signals analarm or trouble condition.Duct smoke sensorSeeDetail AExhaust tubePlugSampling tube(ordered separately)Intakegasket Cover gasket(ordering option)TSD-CO2(ordering option)Sensor housingand electronicsExhaust gasketCouplingSensor coverDetail AMagnetictest/resetswitchAlarmTroublePowerDirtyC08209Fig. 59 -- Smoke Detector SensorSmoke Detector LocationsSupply Air — The Supply Air smoke detector sensor islocated to the left of the unit’s indoor (supply) fan. SeeFig. 60. Access is through the fan access panel. There isno sampling tube used at this location. The sampling tubeinlet extends through the side plate of the fan housing(into a high pressure area). The controller is located on abracket to the right of the return filter, accessed throughthe lift--off filter panel.Smoke Detector SensorC08245Fig. 60 -- Typical Supply Air Smoke Detector SensorLocationReturn Air without Economizer — The sampling tube islocated across the return air opening on the unit basepan.See Fig. 61. The holes in the sampling tube face50TCQA