Installation manual31 EKHBRD011~016ADV1+Y1Indoor unit for air to water heat pump system4P402191-1A – 2015.04The electrical connections on the unit should be done on the optionaldemand PCB.The configuration of pattern B is done by field settings:1 Select the appropriate pattern: [7-02]=12 Turn on multiple set point 1: [7-03]=0 [7-03]=1Turn on multiple set point 2: [7-04]=0 [7-04]=13 Enter the temperature multiple set point 1: [A-03] (see below)Enter the temperature multiple set point 2: [A-04] (see below)Configuration example:Pattern B can also be used to do some primary multi zoning (if all setpoint temperatures are selected the same, no temperature reducingdevice ( ) is required).Multiple thermo ON signals for 3 rooms can be generated. ThermoOFF signals are only valid if all requests are OFF.SetpointFieldsetting Thermo statusSpace 0 65°C RemotecontrollerOFF ON OFF OFF OFFSpace 1 45°C [A-03] OFF ON/OFF ON ON OFFSpace 2 35°C [A-04] OFF ON/OFF OFF ON ONResulting heat pump water OFF 65°C 45°C 45°C 35°CNOTE Leaving water control is not allowed for pattern B. It is the installers responsibility to make sure nounwanted situations can occur (e.g. too highwater temperatures towards floor heating loops,etc.). It is the installers responsibility to make sure thewater circuit is well balanced (e.g. when adomestic hot water request occurs, there will besufficient flow towards other appliances as well,etc.) Daikin does not offer any temperature reducingdevice ( ). This system only provides thepossibility to use multiple set points. When space 0 is in thermo OFF, but space 1 or 2are active, space 0 will be fed with water at atemperature equal to the highest set point ofspaces 1 and 2.This can lead to unwanted heating of space 0.