AKD 5000 Quick Setup Introduction to Quick SetupThis Quick Setup will guide you through EMC correctinstallation of the frequency converter by connectingpower, motor and control wiring (fig. 1). Start/stopof motor is to be done with the switch.Fig. 1 1. Mechanical InstallationAKD 5000 frequency converters allow side-by-side mounting. The necessary cooling demands a freeair passage of 10 cm above and below the frequency converter (5016-5062 380-500 V and 5008-5027200-240 V must have 20 cm).Drill all holes by using the measurements stated in the table. Please note the difference in unit voltage. Placethe frequency converter on the wall. Tighten up all four screws.All the below listed measurements are in mmAKD type A B C a bCompact IP 20, 200–240 V (Fig. 4)5001 - 5003 395 220 160 384 2005004 - 5006 395 220 200 384 2005008 560 242 260 540 2005011 - 5016 700 242 260 680 2005022 - 5027 800 308 296 780 270Compact IP 20, 380–500 V (Fig. 4)5001 - 5005 395 220 160 384 2005006 - 5011 395 220 200 384 2005016 - 5022 560 242 260 540 2005027 - 5032 700 242 260 680 200Compact IP 54, 200–240 V (Fig. 3)5001 - 5003 460 282 195 260 2585004 - 5006 530 282 195 330 2585008 - 5011 810 350 280 560 3265016 - 5027 940 400 280 690 375Compact IP 54, 380–500 V (Fig. 3)5001 - 5005 460 282 195 260 2585006 - 5011 530 282 195 330 2585016 - 5027 810 350 280 560 3265032 - 5062 940 400 280 690 3755042 - 5062 800 308 296 780 270Fig. 2Fig. 3Fig. 4MG.50.R3.02 -6