Control characteristicsResolution of output frequency at 0-590 Hz ±0.003 HzSystem response time (terminals 18, 19, 27, 29, 32, 33) ≤ 2 msSpeed control range (open loop) 1:100 of synchronous speedSpeed accuracy (open loop) 30-4000 RPM: Maximum error of ±8 RPMAll control characteristics are based on a 4-pole asynchronous motorSurroundingsEnclosure, frame size D and E IP00, IP21, IP54Enclosure, frame size F IP21, IP54Vibration test 0.7 gRelative humidity 5% - 95% (IEC 721-3-3; Class 3K3 (non-condensing) during operationAggressive environment (IEC 60068-2-43) H2S test class kDTest method according to IEC 60068-2-43 H2S (10 days)Ambient temperature (at 60 AVM switching mode)- with derating max. 55 °C1)- with full output power, typical EFF2 motors max. 50 °C1)- at full continuous FC output current max. 45 °C1)1) For more information on derating see the Design Guide, section on Special Conditions.Minimum ambient temperature during full-scale operation 0 °CMinimum ambient temperature at reduced performance -10 °CTemperature during storage/transport -25 to +65/70 °CMaximum altitude above sea level without derating 1000 mMaximum altitude above sea level with derating 3000 mDerating for high altitude, see section on special conditions in the Design GuideEMC standards, Emission EN 61800-3, EN 61000-6-3/4, EN 55011, IEC 61800-3EMC standards, ImmunityEN 61800-3, EN 61000-6-1/2,EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6See section on special conditions in the Design Guide!Control card performanceScan interval 5 msControl card, USB serial communicationUSB standard 1.1 (Full speed)USB plug USB type B “device” plugCAUTIONConnection to PC is carried out via a standard host/device USB cable.The USB connection is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.The USB connection is not galvanically isolated from protection earth. Use only isolated laptop/PC as connection to theUSB connector on the frequency converter or an isolated USB cable/converter.Protection and Features• Electronic thermal motor protection against overload.• Temperature monitoring of the heat sink ensures that the frequency converter trips if the temperature reaches apredefined level. An overload temperature cannot be reset until the temperature of the heat sink is below thevalues stated in the tables on the following pages (Guideline - these temperatures may vary for different powersizes, frame sizes, enclosure ratings etc.).• The frequency converter is protected against short-circuits on motor terminals U, V, W.• If a mains phase is missing, the frequency converter trips or issues a warning (depending on the load).• Monitoring of the intermediate circuit voltage ensures that the frequency converter trips if the intermediate circuitvoltage is too low or too high.• The frequency converter is protected against earth faults on motor terminals U, V, W.General Specifications VLT AQUA Drive FC 202 Operation Instructions120 MG20P402 - Rev. 2013-12-1666