[OK]is used for selecting a parameter marked by the cursor andfor enabling the change of a parameter.130BT117.10OKBackInfoWarnAlarmOnCancelIllustration 4.11 Navigation KeysOperation keysfor local control are found at the bottom of the controlpanel.130BP046.10Handon Off Autoon ResetIllustration 4.12 Operation Keys[Hand on]enables control of the frequency converter via the GLCP.[Hand on] also starts the motor, and it is now possible togive the motor speed reference with the navigation keys.The key can be [1] Enabledor [0] Disabled via 0-40 [Handon] Key on LCPThe following control signals are still active when [Handon] is activated:• [Hand on] - [Off] - [Auto on]• Reset• Coasting stop inverse (motor coasting to stop)• Reversing• Set-up select lsb - Set-up select msb• Stop command from serial communication• Quick stop• DC brakeNOTICEExternal stop signals activated by control signals or aserial bus override a “start” command via the LCP.[Off]stops the connected motor. The key can be [1] Enabled or[0] Disabled via 0-41 [Off] Key on LCP If no external stopfunction is selected and the [Off] key is inactive the motorcan only be stopped by disconnecting the mains supply.[Auto on]enables the frequency converter to be controlled via thecontrol terminals and/or serial communication. When astart signal is applied on the control terminals and/or thebus, the frequency converter starts. The key can be [1]Enabled or [0] Disabled via 0-42 [Auto on] Key on LCPNOTICEAn active HAND-OFF-AUTO signal via the digital inputshas higher priority than the control keys [Hand on] –[Auto on].[Reset]is used for resetting the frequency converter after an alarm(trip). The key can be [1] Enabled or [0] Disabled via0-43 [Reset] Key on LCP.The parameter shortcutcan be carried out by holding down the [Main Menu] keyfor 3 seconds. The parameter shortcut allows direct accessto any parameter.4.1.2 How to Operate Numeric LCP (NLCP)The following instructions are valid for the NLCP (LCP 101).The control panel is divided into 4 functional groups,see Illustration 4.13:1. Numeric display2. Menu key and indicator lights (LEDs) - changingparameters and switching between displayfunctions3. Navigation keys and indicator lights (LEDs)4. Operation keys and indicator lights (LEDs)NOTICEParameter copy is not possible with Numeric LocalControl Panel (LCP101).Select one of the following modes:Status Mode: Displays the status of the frequencyconverter or the motor.If an alarm occurs, the NLCP automatically switches tostatus mode.A number of alarms can be displayed.Quick Setup or Main Menu Mode: Display parameters andparameter settings.How to operate the frequenc... VLT AQUA Drive FC 202 Operation InstructionsMG20P402 - Rev. 2013-12-16 734 4