5.11.2 Routing Control CablesProcedure1. Tie down and route all control cables down the left side of the enclosure. See illustration 32.2. Isolate control cables from high-power cables in the drive.3. Connect the shields in a proper way to ensure optimum electrical immunity.4. When the drive is connected to a thermistor, ensure that the thermistor control cable is shielded and reinforced/double insulated.A 24 V DC supply is recommended.5. Connect the control cables to the relevant options on the control card. For more detail, see the relevant fieldbus instructions. Thefieldbus cable must be tied down and routed along with the other control cables inside the unitExample:e30bf715.10Illustration 32: Control Card Cable RoutingElectrical InstallationOperating Guide | VLT® AutomationDrive FC 302AQ275652476278en-000101 / 130R0709| 57Danfoss A/S © 2019.12