Example:e30bg283.1010 mm (0.4)12 13 18 19 27 29 32 33Illustration 36: Connecting a Solid Control Cable to the Terminal BoxIllustration 37: Connecting a Flexible Control Cable to the Terminal Box5.11.6 Disconnecting the Control Cable from the Control TerminalsProcedure1. To open the contact, insert a small screwdriver into the slot between the terminal holes and push the screwdriver inward.2. Pull gently on the wire to free it from the control terminal contact.5.11.7 Enabling Motor OperationContext:If the status line at the bottom of the LCP reads AUTO REMOTE COAST, the unit is ready to operate, but is missing an input signal onterminal 27. Digital input terminal 27 is designed to receive a 24 V DC external interlock command that allows the drive to operatewhen using factory default programming values.Electrical InstallationOperating Guide | VLT® AutomationDrive FC 302AQ275652476278en-000101 / 130R0709| 61Danfoss A/S © 2019.12