Table 11: Digital Input/Output Terminal DescriptionsTerminal Parameter Default setting Description12, 13 – +24 V DC 24 V DC supply voltage for digital inputs and external trans-ducers. Maximum output current 200 mA for all 24 V loads.18 Parameter 5-10 Terminal 18 DigitalInput[8] Start Digital inputs.19 Parameter 5-11 Terminal 19 DigitalInput[10] Reversing32 Parameter 5-14 Terminal 32 DigitalInput[0] No operation33 Parameter 5-15 Terminal 33 DigitalInput[0] No operation27 Parameter 5-12 Terminal 27 DigitalInput[2] Coast inverse For digital input or output. Default setting is input.29 Parameter 5-13 Terminal 29 DigitalInput[14] JOG20 – – Common for digital inputs and 0 V potential for 24 V supply.37 – STO When not using the optional STO feature, a jumper wire is re-quired between terminal 12 (or 13) and terminal 37. This set-up allows the drive to operate with factory default program-ming values.Table 12: Analog Input/Output Terminal DescriptionsTerminal Parameter Default setting Description39 – – Common for analog output.42 Parameter 6-50 Terminal 42 Out-put[0] No operation Programmable analog output. 0–20 mA or 4–20 mA at a maxi-mum of 500 Ω.50 – +10 V DC 10 V DC analog supply voltage for potentiometer or thermistor.15 mA maximum.53 Parameter group 6-1* Analog In-put 1Reference Analog input. For voltage (V) or current (mA).54 Parameter group 6-2* Analog In-put 2Feedback55 – – Common for analog input.5.11.4 Relay Terminals• Relays 1 and 2 are standard relay terminals included on all drives. The location of the outputs depends on the drive configuration.See the Control Shelf section.• If a drive is configured with built-in optional equipment, more terminals may be included. Refer to the manual provided with theoptional equipment.Electrical InstallationOperating Guide | VLT® AutomationDrive FC 302AQ275652476278en-000101 / 130R0709| 59Danfoss A/S © 2019.12