At power-upAt the first power-up the user is asked to choose preferredlanguage. Once selected this screen will never be shownagain in the following powerups, but language can still bechanged in 0-01 Language.130BB628.10Select Language[ 0 ] EnglishSetup 12.3 Menus2.3.1 StatusWhen choosing the [Status] menu it is possible to choosebetween the following:• Motor Frequency (Hz), par. 16-13;• Motor Current (A), par. 16-14;• Motor Speed Reference in Percentage (%), par.16-02;• Feedback, par. 16-52;• Motor Power (kW) (if 0-03 Regional Settings is set to[1] North America, Motor Power will be shown inthe unit of hp instead of kW), par. 16-10 for kW, par.16-11 for hp;• Custom Readout par. 16-09;2.3.2 Quick MenuAllows quick setup of the frequency converter. The mostcommon VLT HVAC Basic Drive functions can beprogrammed here: The [Quick Menu] consists of:• Wizard for open loop applications• Closed loop set-up wizard• Motor set-up• Changes made2.3.3 The FC101 Start-up Wizard for OpenLoop ApplicationsThe built in wizard menu guides the installer through the setup of the frequency converter in a clear and structuredmanner in order to setup an open loop application. A openloop application is here an application with a start signal,analog reference (voltage or current) and optionally alsorelay signals (but no feed back signal from the processapplied).FC+24VDIG INDIG INDIG INDIG INCOM DIG INA OUT / D OUTA OUT / D OUT1819272942555053542012010203040506R2 R1+- 0-10VStart+10VA INA INCOM130BB674.1045ReferenceThe wizard will initially be shown after power up until anyparameter has been changed. The wizard can always beaccessed again through the quick menu. Press [OK] to startthe wizard. If [BACK] is pressed, the FC101 will return to thestatus screen.The wizard will initially start up after power up until aparameter has been changed. The wizard can always beaccessed again through the quick menu. Press [OK] to startthe wizard. If Cancel is pressed, the FC101 will return to thestatus screen.130BB629.10Press OK to start WizardPush Back to skip itSetup 1How to Programme VLT HVAC Basic Drive Programming GuideMG.18.B1.02 - VLT® is a registered Danfoss trademark 132 2