3 Parameters3.1 Main Menu - Operation and Display -Group 0Parameters related to the fundamental functions of thefrequency converter, function of the LCP buttons and config-uration of the LCP display.3.1.1 0-0* Basic Settings0-01 LanguageOption: Function:Defines the language to be used in the display.[0] * English[1] Deutsch[2] Francais[3] Dansk[4] Spanish[5] Italiano[28] Bras.port[255] No Text0-03 Regional SettingsOption: Function:This parameter cannot be adjusted while themotor is running. In order to meet the needs fordifferent default settings in different parts of theworld, 0-03 Regional Settings is implemented inthe frequency converter. The selected settinginfluences the default setting of the motornominal frequency.[0] * Interna-tionalSets default value of 1-23 Motor Frequency[50Hz].[1] NorthAmericaSets the default value of 1-23 Motor Frequency to60Hz.0-04 Operating State at Power-upOption: Function:Select the operating mode upon reconnection ofthe frequency converter to mains voltage afterpower down when operating in Hand (local)mode.[0] * Resume Resumes operation of the frequency convertermaintaining the same local reference and thesame start/stop condition (applied by [Hand On]/[Off] on the LCP or Hand Start via a digital inputas before the frequency converter was powereddown.0-04 Operating State at Power-upOption: Function:[1] Forcedstop,ref=oldUses saved reference [1] to stop the frequencyconverter but at the same time retain the localspeed reference in memory prior to power down.After mains voltage is reconnected and afterreceiving a start command (using the LCP [HandOn] button or Hand Start command via a digitalinput) the frequency converter restarts andoperates at the retained speed reference.0-06 GridTypeOption: Function:Select the grid type of the supplyvoltage/frequency.NOTENot all choices are supported inall power sizes.IT grid is a supply mains, where thereare no connections to ground.Delta is a supply mains where thesecondary part of the transformer isdelta connected and one phase isconnected to ground.[0] 200-240V/50Hz/IT-grid[1] 200-240V/50Hz/Delta[2] 200-240V/50Hz[10] 380-440V/50Hz/IT-grid[11] 380-440V/50Hz/Delta[12] 380-440V/50Hz[20] 440-480V/50Hz/IT-grid[21] 440-480V/50Hz/Delta[22] 440-480V/50Hz[30] 525-600V/50Hz/IT-grid[31] 525-600V/50Hz/Delta[32] 525-600V/50Hz[100] 200-240V/60Hz/IT-grid[101] 200-240V/60Hz/Delta[102] 200-240V/60Hz[110] 380-440V/60Hz/IT-grid[111] 380-440V/60Hz/Delta[112] 380-440V/60HzParameters VLT HVAC Basic Drive Programming Guide20 MG.18.B1.02 - VLT® is a registered Danfoss trademark33