9-23 Parameters for SignalsArray [1000]Option: Function:[1692] Warning Word[1693] Warning Word 2[1694] Ext. Status Word[1695] Ext. Status Word 2[1696] Maintenance Word[1830] Analog Input X42/1[1831] Analog Input X42/3[1832] Analog Input X42/5[1833] Analog Out X42/7 [V][1834] Analog Out X42/9 [V][1835] Analog Out X42/11 [V][1836] Analog Input X48/2 [mA][1837] Temp. Input X48/4[1838] Temp. Input X48/7[1839] Temp. Input X48/10[1850] Sensorless Readout [unit][1860] Digital Input 2[2013] Minimum Reference/Feedb.[2014] Maximum Reference/Feedb.[2021] Setpoint 1[2022] Setpoint 2[2023] Setpoint 3[2643] Terminal X42/7 Bus Control[2653] Terminal X42/9 Bus Control[2663] Terminal X42/11 Bus Control9-27 Parameter EditOption: Function:Parameters can be edited via PROFIBUS, thestandard RS485 interface, or the LCP.[0] Disabled Disables editing via PROFIBUS.[1] * Enabled Enables editing via PROFIBUS.9-28 Process ControlOption: Function:Process control (setting of control word, speedreference, and process data) is possible via eitherPROFIBUS or standard fieldbus, but not bothsimultaneously. Local control is always possiblevia the LCP. Control via process control is possiblevia either terminals or fieldbus depending on thesettings in parameter 8-50 Coasting Select toparameter 8-56 Preset Reference Select.[0] Disable Disables process control via PROFIBUS, andenables process control via standard fieldbus orPROFIBUS master class 2.[1]*EnablecyclicmasterEnables process control via PROFIBUS master class1, and disables process control via standardfieldbus or PROFIBUS master class 2.9-53 Profibus Warning WordRead onlyRange: Function:0* [0 - 65535 ] This parameter displays PROFIBUS communi-cation warnings. Refer to the PROFIBUSOperating Instructions for further information.Bit Meaning0 Connection with DP-master is not OK.1 Not used.2 FDL (fieldbus data link layer) is not OK.3 Clear data command received.4 Actual value is not updated.5 Baudrate search.6 PROFIBUS ASIC is not transmitting.7 Initialisation of PROFIBUS is not OK.8 Frequency converter is tripped.9 Internal CAN error.10 Wrong configuration data from PLC.11 Wrong ID sent by PLC.12 Internal error occured.13 Not configured.14 Time-out active.15 Warning 34 active.Table 3.15 PROFIBUS Warning Word9-63 Actual Baud RateOption: Function:This parameter displays the actualPROFIBUS baud rate. The PROFIBUSmaster automatically sets the baudrate.[0] 9,6 kbit/s[1] 19,2 kbit/s[2] 93,75 kbit/s[3] 187,5 kbit/s[4] 500 kbit/s[6] 1500 kbit/s[7] 3000 kbit/s[8] 6000 kbit/s[9] 12000 kbit/s[10] 31,25 kbit/s[11] 45,45 kbit/s[255] * No baudrate found9-65 Profile NumberRange: Function:0* [0 - 0 ] This parameter contains the profile identification.Byte 1 contains the profile number and byte 2 theversion number of the profile.Parameter Descriptions Programming GuideMG11CE02 Danfoss A/S © 03/2015 All rights reserved. 993 3