13-11 Comparator OperatorArray [6]Option: Function:mately equal to the fixed value inparameter 13-12 Comparator Value.[2] > Select [2] > for the inverse logic of option [0] <.[5] TRUElongerthan..[6] FALSElongerthan..[7] TRUEshorterthan..[8] FALSEshorterthan..13-12 Comparator ValueArray [6]Range: Function:Sizerelated*[-100000 -100000 ]Enter the trigger level for thevariable that is monitored by thiscomparator. This is an arrayparameter containing comparatorvalues 0 to 5.3.13.4 13-2* TimersUse the result (TRUE or FALSE) from timers directly todefine an event (see parameter 13-51 SL Controller Event), oras boolean input in a logic rule (see parameter 13-40 LogicRule Boolean 1, parameter 13-42 Logic Rule Boolean 2, orparameter 13-44 Logic Rule Boolean 3). A timer is only FALSEwhen started by an action (for example [29] Start timer 1)until the timer value entered in this parameter has elapsed.Then it becomes TRUE again.All parameters in this parameter group are arrayparameters with index 0 to 2. Select index 0 to programmetimer 0, select index 1 to programme timer 1, and so on.13-20 SL Controller TimerArray [3]Range: Function:Sizerelated*[ 0 -0 ]Enter the value to define the duration ofthe FALSE output from the programmedtimer. A timer is only FALSE if it is startedby an action (for example [29] Start timer1) and until the given timer value haselapsed.3.13.5 13-4* Logic RulesCombine up to 3 boolean inputs (TRUE/FALSE inputs) fromtimers, comparators, digital inputs, status bits, and eventsusing the logical operators AND, OR, and NOT. Selectboolean inputs for the calculation in parameter 13-40 LogicRule Boolean 1, parameter 13-42 Logic Rule Boolean 2, andparameter 13-44 Logic Rule Boolean 3. Define the operatorsused to logically combine the selected inputs inparameter 13-41 Logic Rule Operator 1 andparameter 13-43 Logic Rule Operator 2.. . .. . . . . .. . .Par. 13-43Logic Rule Operator 2Par. 13-41Logic Rule Operator 1Par. 13-40Logic Rule Boolean 1Par. 13-42Logic Rule Boolean 2Par. 13-44Logic Rule Boolean 3130BB673.10Illustration 3.36 Logic RulesPriority of calculationThe results of parameter 13-40 Logic Rule Boolean 1,parameter 13-41 Logic Rule Operator 1, andparameter 13-42 Logic Rule Boolean 2 are calculated first.The outcome (TRUE/FALSE) of this calculation is combinedwith the settings of parameter 13-43 Logic Rule Operator 2and parameter 13-44 Logic Rule Boolean 3, yielding the finalresult (TRUE/FALSE) of the logic rule.13-40 Logic Rule Boolean 1Array [6]Option: Function:[0] False Enters the fixed value of FALSE in thelogic rule.[1] True Enters the fixed value TRUE in the logicrule.[2] Running See chapter 3.7.3 5-3* Digital Outputsfor further description.[3] In range See chapter 3.7.3 5-3* Digital Outputsfor further description.[4] On reference See chapter 3.7.3 5-3* Digital Outputsfor further description.[5] Torque limit See chapter 3.7.3 5-3* Digital Outputsfor further description.[6] Current Limit See chapter 3.7.3 5-3* Digital Outputsfor further description.[7] Out of currentrangeSee chapter 3.7.3 5-3* Digital Outputsfor further description.[8] Below I low See chapter 3.7.3 5-3* Digital Outputsfor further description.Parameter Descriptions Programming GuideMG11CE02 Danfoss A/S © 03/2015 All rights reserved. 1113 3