10.12 Parameter Group 8-** Relay OutputsTable 137: 8-1 - Relay A FunctionOption FunctionSelects the function of Relay A.Relay A is a changeover relay.Off Relay A is not used.Ready The relay is closed when the soft starter is in Ready state.* Run The Run output closes when the soft start is complete (when the starting current drops below 120% ofthe programmed motor full load current). The output remains closed until the beginning of a stop (eithersoft stop or coast to stop).Warning The relay closes when the soft starter issues a warning.Trip The relay closes when the starter trips.Low Current Flag The relay closes when the low current flag activates while the motor is running (see parameter 8-7 LowCurrent Flag).High Current Flag The relay closes when the high current flag activates while the motor is running (see parameter 8-8 HighCurrent Flag).Motor Tempera-ture FlagThe relay closes when the motor temperature flag activates (see parameter 8-9 Motor Temperature Flag).Soft Brake Relay The relay closes when the soft starter receives a stop signal, and remains closed until the end of softbrake.Reversing Contac-torThe relay controls an external contactor, for reverse operation.Table 138: 8-2 - Relay A On DelayRange Function* 0 s 0:00–5:00 (minutes:seconds) Sets the delay for changing the state of Relay A.Table 139: 8-3 - Relay A Off DelayRange Function* 0 s 0:00–5:00 (minutes:seconds) Sets the delay for changing the state of Relay A.Table 140: 8-4 - Relay B FunctionOption FunctionSelects the function of Relay B (normally open).See parameter 8-1 Relay A Function for details.OffReady* RunWarningProgrammable ParametersOperating Guide | VLT® Soft Starter MCD 600AQ262141844215en-000202 / 175R1174100 | Danfoss A/S © 2018.10