10.10 Parameter Group 6-** Protection ActionTable 106: 6-1 - Auto-Reset CountRange Function*0 0–5 Sets how many times the soft starter auto-resets if it continues to trip.The reset counter increases by 1 each time the soft starter auto-resets, and resets after a successful start.Setting this parameter to 0 disables auto-reset.Table 107: 6-2 - Auto-Reset DelayRange Function*5 s 0:05–15:00 (minutes:seconds) Sets a delay before the soft starter auto-resets a trip.Table 108: 6-3 - Current ImbalanceOption FunctionSelects the soft starter's response to each protection.All protection events are written to the event log.* Soft Trip andLogThe soft starter stops the motor as selected in parameter 2-9 Stop Mode or parameter 3-11 Stop Mode, thenenters trip state. The trip must be reset before the soft starter can restart.Soft Trip andResetThe soft starter stops the motor as selected in parameter 2-9 Stop Mode or parameter 3-11 Stop Mode, thenenters trip state. The trip resets after the auto-reset delay.Trip Starter The soft starter removes power and the motor coasts to stop. The trip must be reset before the soft startercan restart.Trip and Reset The soft starter removes power and the motor coasts to stop. The trip resets after the auto-reset delay.Warn and Log The protection is written to the event log and the display shows a warning message, but the soft starter con-tinues to operate.Log Only The protection is written to the event log but the soft starter continues to operate.Table 109: 6-4 - UndercurrentOption FunctionSelects the soft starter's response to the protection event.* Soft Trip and LogSoft Trip and ResetTrip StarterTrip and ResetWarn and LogLog OnlyProgrammable ParametersOperating Guide | VLT® Soft Starter MCD 600AQ262141844215en-000202 / 175R1174 | 91Danfoss A/S © 2018.10