Option FunctionLate DecelerationTable 38: 2-12 - Adaptive Control GainRange Function* 75% 1–200% Adjusts the performance of adaptive control. This setting affects both starting and stopping control.Table 39: 2-13 - Multi PumpOption FunctionAdjusts the performance of adaptive control to suit installations with multiple pumps connected to a com-mon outlet manifold.* Single PumpManifold PumpTable 40: 2-14 - Start DelayRange Function* 0 s 0:00–60:00 (minutes:seconds) Sets a delay after the soft starter receives a start command before it starts the motor.Table 41: 2-15 - DC Brake TorqueRange Function* 20% 20–100% Sets the amount of brake torque the soft starter uses to slow the motor.Table 42: 2-16 - DC Brake TimeRange Function* 1 s 0:01–0:30 (minutes:seconds) Sets the duration for DC injection during a braking stop.Table 43: 2-17- Brake Current LimitRange Function* 250% 100–600% FLC Sets the current limit for soft brake.Table 44: 2-18 - Soft Brake DelayRange Function*400 ms 400–2000msSets the time which the soft starter waits after a stop signal is received before it begins to supply brakingcurrent to the motor. Set to allow time for K1 and K2 to switch.10.7 Parameter Group 3-** Motor Start/Stop-2The parameters in this group control the operation of the secondary configuration of the motor. Use the programmable input to selectthe active motor set.Programmable ParametersOperating Guide | VLT® Soft Starter MCD 600AQ262141844215en-000202 / 175R1174 | 81Danfoss A/S © 2018.10