Table 85: 4-22 - Saturday ModeOption FunctionEnables or disables auto-start/stop for Saturday.* Start/Stop DisableStart Only EnableStop Only EnableStart/Stop EnableTable 86: 4-23 - Saturday Start TimeRange Function*00:00 00:00–23:59 Sets the auto-start time for Saturday (24-hour format).Table 87: 4-24 - Saturday Stop TimeRange Function*00:00 00:00–23:59 Sets the auto-stop time for Saturday (24-hour format).10.9 Parameter Group 5-** Protection LevelsTable 88: 5-1 - Current ImbalanceRange Function*30% 10–50% Sets the trip point for current imbalance protection.Table 89: 5-2 - Current Imbalance DelayRange Function*3 s 0:00–4:00 (minutes:seconds) Slows the soft starter's response to current imbalance, avoiding trips due to momentary fluc-tuations.Table 90: 5-3 - UndercurrentRange Function*20% 0–100% Sets the trip point for undercurrent protection as a percentage of motor full load current. Set to a level betweenthe motor's normal working range and the motor's magnetizing (no load) current (typically 25–35% of FLC). Asetting of 0% disables undercurrent protection.Table 91: 5-4 - Undercurrent DelayRange Function* 5 s 00–4:00 (minutes:seconds) Slows the soft starter's response to undercurrent, avoiding trips due to momentary fluctua-tions.Programmable ParametersOperating Guide | VLT® Soft Starter MCD 600AQ262141844215en-000202 / 175R117488 | Danfoss A/S © 2018.10