EXAMPLE 3:Variable value= REFERENCE, range= Min ref - Max refRange needed for output= Min ref (0%) - Max ref (100%), 0–10 mAOutput signal 0 or 4 mA is needed at Min ref - set par.6-51Terminal 42 Output Min Scale to 0%Output signal 10 mA is needed at Max ref (100% of range) - set par.6-52Terminal 42 Output Max Scale to 200%(20 mA / 10 mA x 100%=200%).