[1006] Readout Receive Error Counter View the number of CAN control receipt errors since the last power-up.[1007] Readout Bus-off Counter View the number of bus-off events since the last power-up.[1013] Warning Parameter View a DeviceNet-specific warning word. One separate bit is assigned to every warning.[1115] LON Warning Word Shows the LON-specific warnings.[1117] XIF Revision Shows the version of the external interface file of the Neuron C chip on the LON option.[1118] LON Works Revision Shows the software version of the application program of the Neuron C chip on the LON option.[1500] Operating Hours View the number of running hours of the adjustable frequency drive.[1501] Running Hours View the number of running hours of the motor.[1502] kWh Counter View the line power consumption in kWh.[1600] Control Word View the control word sent from the adjustable frequency drive via the serial communication portin hex code.[1601] * Reference [Unit] Total reference (sum of digital/analog/preset/bus/freeze ref./catch up and slow-down) in selectedunit.[1602] Reference % Total reference (sum of digital/analog/preset/bus/freeze ref./catch up and slow-down) as a per-centage.[1603] Status Word Present status word[1605] Main Actual Value [%] One or more warnings in a Hex code[1609] Custom Readout View the user-defined readouts as defined in par. 0-30, 0-31 and 0-32.[1610] Power [kW] Actual power consumed by the motor in kW.[1611] Power [hp] Actual power consumed by the motor in HP.[1612] Motor Voltage Voltage supplied to the motor.[1613] Motor Frequency Motor frequency, i.e., the output frequency from the adjustable frequency drive in Hz.[1614] Motor Current Phase current of the motor measured as effective value.[1615] Frequency [%] Motor frequency, i.e., the output frequency from the adjustable frequency drive as a percentage.[1616] Torque [Nm] Present motor load as a percentage of the rated motor torque.[1617] Speed [RPM] Speed in RPM (revolutions per minute), i.e., the motor shaft speed in closed-loop based on theentered motor nameplate data, the output frequency and the load on the adjustable frequency drive.[1618] Motor Thermal Thermal load on the motor, calculated by the ETR function. See also parameter group 1-9* MotorTemperature.[1622] Torque [%] Shows the actual torque produced as a percentage.[1630] DC Link Voltage Intermediate circuit voltage in the adjustable frequency drive.[1632] BrakeEnergy/s Present braking energy transferred to an external brake resistor.Stated as an instantaneous value.[1633] BrakeEnergy/2 min Braking energy transferred to an external brake resistor. The mean power is calculated continuouslyfor the latest 120 seconds.[1634] Heatsink Temp. Present heatsink temperature of the adjustable frequency drive. The cut-out limit is 203 ± 9°F (95± 5°C); cutting back in occurs at 158 ± 9°F (70 ± 5°C).[1635] Thermal Drive Load Percentage load of the inverters[1636] Inv. Nom. Current Nominal current of the adjustable frequency drive.[1637] Inv. Max. Current Maximum current of the adjustable frequency drive.[1638] SL Control State State of the event executed by the control.[1639] Control Card Temp. Temperature of the control card.[1650] External Reference Sum of the external reference as a percentage, i.e., the sum of analog/pulse/bus.[1652] Feedback [Unit] Signal value in units from the programmed digital input(s).[1653] Digi Pot Reference View the contribution of the digital potentiometer to the actual reference feedback.8 How to program the adjustable frequencydriveVLT® AQUA DriveInstruction Manual8-10 MG.20.M5.22 - VLT® is a registered Danfoss trademark8