6-01 Live Zero Timeout FunctionOption: Function:Select the timeout function. The function set in par.6-01Live Zero Timeout Function will be activatedif the input signal on terminal 53 or 54 is below 50% of the value in par.6-10Terminal 53 LowVoltage, par. 6-12Terminal 53 Low Current, par.6-20Terminal 54 Low Voltage or par. 6-22Terminal54 Low Current for a time period defined in par.6-00Live Zero Timeout Time. If several timeoutsoccur simultaneously, the adjustable frequency drive prioritizes the timeout functions as follows:1. par.6-01Live Zero Timeout Function2. par. 8-04Control Timeout FunctionThe output frequency of the adjustable frequency drive can be:• [1] frozen at the present value• [2] overruled to stop• [3] overruled to jog speed• [4] overruled to max. speed• [5] overruled to stop with subsequent tripIf you select set-up 1-4, par. 0-10Active Set-up must be set toMulti Set-up, [9].This parameter cannot be adjusted while the motor is running.[0] * Off[1] Freeze output[2] Stop[3] Jogging[4] Max. speed[5] Stop and trip6-10 Terminal 53 Low VoltageRange: Function:0.07 V* [0.00 - par. 6-11 V] Enter the low voltage value. This analog input scaling value should correspond to the low reference/feedback value set in par.6-14Terminal 53 Low Ref./Feedb. Value.6-11 Terminal 53 High VoltageRange: Function:10.00 V* [par. 6-10 - 10.00 V] Enter the high voltage value. This analog input scaling value should correspond to the high refer-ence/feedback value set in par.6-15Terminal 53 High Ref./Feedb. Value.VLT® AQUA DriveInstruction Manual8 How to program the adjustable frequencydriveMG.20.M5.22 - VLT® is a registered Danfoss trademark 8-298