Operatingtemperature de-ratingSpecifications35 °C to 40 °C (95°F to 104 °F)Maximum temperature is reduced by 1°C/175 m (1°F/319 ft) above 950 m (3,117 ft).40 °C to 45 °C(104 °F to 113 °F)Maximum temperature is reduced by 1°C/125 m (1°F/228 ft) above 950 m (3,117 ft).The following section defines the limits to help avoid IT equipment damage and/or failure fromparticulates and gaseous contamination. If the levels of particulates or gaseous pollution are beyond thespecified limits and cause equipment damage or failure, you may need to rectify the environmentalconditions. Remediation of environmental conditions is the responsibility of the customer.ParticulatecontaminationSpecificationsAir filtration Data center air filtration as defined by ISO Class 8 per ISO 14644-1 with a 95%upper confidence limit.NOTE: Applies to data center environments only. Air filtration requirements donot apply to IT equipment designed to be used outside a data center, inenvironments such as an office or factory floor.NOTE: Air entering the data center must have MERV11 or MERV13 filtration.Conductive dust Air must be free of conductive dust, zinc whiskers, or other conductive particles.NOTE: Applies to data center and non-data center environments.Corrosive dust • Air must be free of corrosive dust.• Residual dust present in the air must have a deliquescent point less than 60%relative humidity.NOTE: Applies to data center and non-data center environments.GaseouscontaminationSpecificationsCopper couponcorrosion rate<300 Å/month per Class G1 as defined by ANSI/ISA71.04-1985.Silver couponcorrosion rate<200 Å/month as defined by AHSRAE TC9.9.NOTE: Maximum corrosive contaminant levels measured at ≤50% relative humidity.167