Ch a pt er 11 DeviceNet Re m ote I/O Module AHRTU-DNET11-101Notes:1. Write 16#0002 to D1006 for always reading the word device; write 16#0001 to D1006 for onlyreading once. Write 16#0002 to D1007 for always writing to word device and write 16#001 toD1007 for only writing once.2. Write 16#0200 to D1006 for always reading bit device and write 16#0100 to D1006 for onlyreading once. Write 16#0200 to D1007 for always writing to bit device and write 16#0100 toD1007 for only writing once.3. Writing 1 to D1011 indicates to trigger and execute the content of Group ID 1. After theexecution is over, D1011 is cleared as 0. If the default value in D1011 is 0, no group will betriggered.4. Write the number of times to D1013. If the number 0 is written, no execution or the stoppingstate occurs; 1~254 can be the execution times; 255 (16#FF) indicates the action is alwaysexecuted.11.6.3.2 Monitoring via the SoftwareOn the AHRTU-DNET-5A configuration interface, click “Start Monitor” button to monitor theoperational state of AH10SCM-5A.