UPS System InstallationEaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual 4-9Figure 4-10. Interface Terminal Detail (Terminal Cover Removed)Figure 4-11. Building Alarm Terminal Block Connector AssignmentsTable 4-1. Building Alarm ConnectionsBuilding Alarm Terminal Name Description1 Building Alarm 1 + Input: Programmable UPS alarm, activated by a remote dry contact closure.2 Building Alarm 1 –3 Building Alarm 2 + Input: Programmable UPS alarm, activated by a remote dry contact closure.4 Building Alarm 2 –5 Building Alarm 3 + Input: Programmable UPS alarm, activated by a remote dry contact closure.6 Building Alarm 3 –9E 160-200 kVA9E 80-120 kVABuilding Alarm 1 Building Alarm 3Building Alarm 2Mini-SlotCommunication Bay 1Mini-SlotCommunication Bay 2Mini-SlotCommunication Bay 1Building Alarm(See Figure 4-11 for Detail) Building Alarm(See Figure 4-11 for Detail)REPO Terminals(See Figure 4-16 for Detail) REPO Terminals(See Figure 4-16 for Detail)Parallel CAN Output (RJ45)Parallel CAN Output (RJ45)Pull chain Terminals Pull chain TerminalsParallel CAN Input (RJ45) Parallel CAN Input (RJ45)Mini-SlotCommunication Bay 24-115 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 A02THIS DOCUMENT, INCLUDING THE DRAWING AND INFORMATION CONTAINED THEREON, IS CONFIDENTIAL AND IS THE EXCLUSIVE PROPERTY OF EATON CORPORATION, AND IS MERELY ON LOAN AND SUBBY EATON AT ANY TIME. BY TAKING POSSESSION OF THIS DOCUMENT, THE RECIPIENT ACKNOWLEDGES AND AGREES THAT THIS DOCUMENT CANNOT BE USED IN ANY MANNER ADVERSE TO THE INTEREAND THAT NO PORTION OF THIS DOCUMENT MAY BE COPIED OR OTHERWISE REPRODUCED WITHOUT THE PRIOR WRITTEN CONSENT OF EATON. IN THE CASE OF CONFLICTING CONTRACTUAL PROVISIONOTICE SHALL GOVERN THE STATUS OF THIS DOCUMENT.NOTICE TO PERSONS RECEIVING THIS DOCUMENT AND/OR TECHNICAL INFORMATIONEATON CORPORATION - CONFIDENTIAL AND PROPRIETARYAPPROVED:4-10-4-11PRO-E DRAWINGSAFETY:STATE:DOCUMENT TYPE:CHECKED:MODIFIED:REVISION:NAME:ECO:ORIGINATED:DESCRIPTION:DIMENSIONS ARE IN MILLIMETERS AFTER PLATING, DIMENSIONS AND TOLERANCES IN ACCORDANCE WITH ASME Y14.5M-1994. SEE NOTES FOR TOLERANCES.EATON CORPORATIONTHIRD PROJECTIONMETRIC4-104-11dle plateMini-Slot Communication BaysInterface TerminalsOpen the doorBuilding AlarmSee figure 4-12 for detailREPO TerminalsSee figure 4-12 for detailPull Chain TerminalsSee figure 4-12 for detailParallel CAN Input (RJ45)Parallel CAN Input (RJ45)Mini-SlotCommunication Bay 2Mini-SlotCommunication Bay 1