Operating Instructions6.9 Self-test Mode• This function is only available at access level 3.• Enter the access code 2321.• Press the “Test” button (2).• The Test indicator will slow flash and the buzzer will give aslow pulsing tone.• The fire indicator on every detector head will turn on.• This function is useful for checking that each head is fittedcorrectly as the fire indicator will not turn on.• To end the self-test mode, enter the access code 2321and press button 2.6.10 Walk Test Mode• This function is only available at access level 3.• Enter the access code 2321• Press “Indicator Test” button (3).• The Test indicator will turn on and the buzzer will give aslow pulsing tone.• This function places all zones in test mode and is usedduring commissioning to test every fire detection deviceon a zone.• Repeat the following for each zone (with fire detectiondevices) in turn:• Activate the fire detection device or manual call point onthe zone.• All fire alarm devices will sound on all zones for 3seconds and then will automatically silence.• The fire panel will then reset the zone from the firecondition.• Repeat the above process until all fire detection deviceand manual call points on the zone have been tested.• To end the walk test mode enter the access code 3112 or2321 and press the “Reset” button.• If no fire detection device or manual call point is triggeredwithin 10 minutes of the walk test being started, the testmode will timeout and return back to access level 1/normalcondition.www.acornfiresecurity.comwww.acornfiresecurity.com