DESCRIPTION:DATE:DRAWING NO: 1 of 1SHEET:REVISION: B 070804PHYSICAL FEATURES AND REQUIREMENTS164201536-2Installation InformationA-4 EATON Powerware ® 9390 Integrated Battery Cabinet (Models IBC-S and IBC-L) Installation Manual 164201536 Rev Dwww.eaton.com/powerquality1. The battery cabinet operating environment must meet the weight requirements shown inTable A and size requirements shown on Drawing 164201536-9.2. The battery cabinets are palleted separately for shipping.3. Do not tilt cabinets more than 10° during handling.4. Dimensions are in millimeters (inches).Table A. Equipment WeightComponentWeightkg (lb)Shipping Installed Point LoadingIBC-S with 32 batteries (384 VDC) 837 (1845) 807 (1780) 4 at 202 (445)IBC-S with 36 batteries (432 VDC) 909 (2005) 880 (1940) 4 at 220 (485)IBC-S with 40 batteries (480 VDC) 982 (2165) 953 (2100) 4 at 238 (525)IBC-L with 32 batteries (384 VDC) 1848 (4075) 1814 (4000) 8 at 227 (500)IBC-L with 36 batteries (432 VDC) 2029 (4475) 1995 (4400) 8 at 249 (550)IBC-L with 40 batteries (480 VDC) 2211 (4875) 2177 (4800) 8 at 272 (600)5. The clearances required around the battery cabinets are shown in Table B.Table B. Battery Cabinet ClearancesFrom Top of Cabinet Minimum clearance over the battery cabinet is457.2 mm (18 in.) for ventilationFrom Front of Cabinet 36 inches (0.9144m) working spaceFrom Back of Cabinet None requiredFrom Right Side of Cabinet None requiredFrom Left Side of Cabinet None required6. The basic environmental requirements of both Models IBC-S and IBC-L for operation ofthe UPS system are:Operational Temperature Range: 22-28°C (72-82°F)Maximum Relative Humidity: 95%, noncondensingCAUTION: It is recommended for optimal battery life and discharge performance to keep the ambient air temperature the battery is used in at 25°C (77°F).