DESCRIPTION:DATE:DRAWING NO: 2 of 3SHEET:REVISION: C 032406BATTERY WIRING INSTALLATION NOTES164201536-5Installation InformationA-10 EATON Powerware ® 9390 Integrated Battery Cabinet (Models IBC-S and IBC-L) Installation Manual 164201536 Rev Dwww.eaton.com/powerquality11. The battery cabinet external wiring requirements are shown in Tables D and E.Table D. Battery Cabinet External Wiring and Termination Requirements (UPS‐to‐Battery,Battery‐to‐Battery, or Remote Disconnect to Battery) for Powerware 9390 Model IBC-SUPSModelkVABatteryTypeNumberofCabinetsCabinetPositionWireSizeUPS toBatteryWireSizeBattery toBatteryTerminations TorqueNm (lb in)Size andType Screw40 and50 Note 2 1, 2, 3,or 4Line‐up‐and‐MatchSupplied1 per PoleSupplied1 per Pole1 - #6-500 kcmil2 - 1 Bolt Mounting56.5 (500)22.6 (200)1/2 Allen3/8 Hex nut40 and50 Note 2 1, 2, 3,or 4Standalone1/01 per Pole1/01 per Pole1 - #6-500 kcmil2 - 1 Bolt Mounting56.5 (500)22.6 (200)1/2 Allen3/8 Hex nut60 Note 2 1, 2, 3,or 4Line‐up‐and‐MatchSupplied1 per PoleSupplied1 per Pole1 - #6-500 kcmil2 - 1 Bolt Mounting56.5 (500)22.6 (200)1/2 Allen3/8 Hex nut60 Note 2 1, 2, 3,or 4Standalone2/01 per Pole2/01 per Pole1 - #6-500 kcmil2 - 1 Bolt Mounting56.5 (500)22.6 (200)1/2 Allen3/8 Hex nut80 Note 2 1, 2, 3,or 4Line‐up‐and‐MatchSupplied1 per PoleSupplied1 per Pole1 - #6-500 kcmil2 - 1 Bolt Mounting56.5 (500)22.6 (200)1/2 Allen3/8 Hex nut80 Note 2 1, 2, 3,or 4Standalone3/01 per Pole3/01 per Pole1 - #6-500 kcmil2 - 1 Bolt Mounting56.5 (500)22.6 (200)1/2 Allen3/8 Hex nutNOTE 1:1All specified wire sizes are 90C rated copper minimum.NOTE 2: Replace with same type and number of original battery. Mixing battery letter designation and or sizes willdamage equipment and void warranty.