DESCRIPTION:DATE:DRAWING NO: 3 of 3SHEET:REVISION: C 032406BATTERY WIRING INSTALLATION NOTES164201536-5Installation InformationA-11EATON Powerware ® 9390 Integrated Battery Cabinet (Models IBC-S and IBC-L) Installation Manual 164201536 Rev Dwww.eaton.com/powerqualityTable E. Battery Cabinet External Wiring and Termination Requirements (UPS‐to‐Battery,Battery‐to‐Battery, or Remote Disconnect to Battery) for Powerware 9390 Model IBC-LUPSModelkVABatteryTypeNumberofCabinetsCabinetPositionWireSizeUPS toBatteryWireSizeBattery toBatteryTerminations TorqueNm (lb in)Size andType Screwor Bolt40 and50 Note 2 1, 2, 3,or 4Line‐up‐and‐MatchSupplied1 per PoleSupplied1 per Pole2 - #2-600 kcmil2 - 1 Bolt Mounting42.4 (375)22.6 (200)3/8 HexM10 Hex40 and50 Note 2 1, 2, 3,or 4Standalone1/01 per Pole1/01 per Pole2 - #2-600 kcmil2 - 1 Bolt Mounting42.4 (375)22.6 (200)3/8 HexM10 Hex60 Note 2 1, 2, 3,or 4Line‐up‐and‐MatchSupplied1 per PoleSupplied1 per Pole2 - #2-600 kcmil2 - 1 Bolt Mounting42.4 (375)22.6 (2003/8 HexM10 Hex60 Note 2 1, 2, 3,or 4Standalone2/01 per Pole2/01 per Pole2 - #2-600 kcmil2 - 1 Bolt Mounting42.4 (375)22.6 (2003/8 HexM10 Hex80 Note 2 1, 2, 3,or 4Line‐up‐and‐MatchSupplied1 per PoleSupplied1 per Pole2 - #2-600 kcmil2 - 1 Bolt Mounting42.4 (375)22.6 (200)3/8 HexM10 Hex80 Note 2 1, 2, 3,or 4Standalone3/01 per Pole3/01 per Pole2 - #2-600 kcmil2 - 1 Bolt Mounting42.4 (375)22.6 (200)3/8 HexM10 Hex100 Note 2 1, 2, 3,or 4Line‐up‐and‐MatchSupplied2 per PoleSupplied2 per Pole2 - #2-600 kcmil2 - 1 Bolt Mounting42.4 (375)22.6 (200)3/8 HexM10 Hex100 Note 2 1, 2, 3,or 4Standalone2/02 per Pole2/02 per Pole2 - #2-600 kcmil2 - 1 Bolt Mounting42.4 (375)22.6 (200)3/8 HexM10 Hex120 Note 2 1, 2, 3,or 4Line‐up‐and‐MatchSupplied2 per PoleSupplied2 per Pole2 - #2-600 kcmil2 - 1 Bolt Mounting42.4 (375)22.6 (200)3/8 HexM10 Hex120 Note 2 1, 2, 3,or 4Standalone3/02 per Pole3/02 per Pole2 - #2-600 kcmil2 - 1 Bolt Mounting42.4 (375)22.6 (200)3/8 HexM10 Hex160 Note 2 1, 2, 3,or 4Line‐up‐and‐MatchSupplied2 per PoleSupplied2 per Pole2 - #2-600 kcmil2 - 1 Bolt Mounting42.4 (375)22.6 (200)3/8 HexM10 Hex160 Note 2 1, 2, 3,or 4Standalone250 kcmil2 per Pole250 kcmil2 per Pole2 - #2-600 kcmil2 - 1 Bolt Mounting42.4 (375)22.6 (200)3/8 HexM10 HexNOTE 1: All specified wire sizes are 90C rated copper minimum.NOTE 2: Replace with same type and number of original battery. Mixing battery letter designation and or sizes willdamage equipment and void warranty.