IQ 100 Series (130/140/150) MeterOverview &Specifications12 User and Installation Manual IM02601003E-July 2010 www.eaton.comCurrent InputsThe IQ 100 Series meter’s Current Inputs use a unique dual input method:Method 1: CT Pass Through•The CT passes directly through the meter without any physical termination on the meter. Thisinsures that the meter cannot be a point of failure on the CT circuit. This is preferable for utilityusers when sharing relay class CTs. No Burden is added to the secondary CT circuit.Method 2: Current “Gills”.•This unit additionally provides ultra-rugged Termination Pass Through Bars that allow CT leads tobe terminated on the meter. This, too, eliminates any possible point of failure at the meter. Thisis a preferred technique for insuring that relay class CT integrity is not compromised (the CT willnot open in a fault condition).Ordering InformationIQ - 150 - M - A - 6 - 5 - 1 - 11 2 3 4 5 61. Model:130 = Volts/Amps Meter140 = Power Meter150 = Energy Meter2. Meter TypeM = Meter (with integral display)T = Transducer Only (no display, RS485 Modbus and KYZ Pulse Output are standard with type T)3. Frequency:5 = 50 Hz System6 = 60 Hz System4. Current Input:5 = 5 Amp Secondary1 = 1 Amp Secondary5. Power Supply:1 = Universal, (90 - 265) VAC @50/60Hz or (100-370) VDC4 = (18 - 60) VDC6. Communication0 = None1 = RS485 Modbus and KYZ Pulse OutputExample: IQ 150-M-A-6-5-1-1(IQ 150 Energy Meter with 60 Hz System, 5 Amp Secondary, 90-265 VAC/100-370 VDC Power Supply, RS485Modbus and KYZ Pulse Output)